58TN0B/58TN1B: Installation, Start–Up, Operating and Service and Maintenance Instructions
12. Configure Dehumidify function to remove 24 VAC from Dehum
terminal on a demand to dehumidify. Consult thermostat
installation instructions for more information.
13. Thermostat terminal connection order on furnace control may vary-
reference furnace control labeling for designations.
Field installed jumper required for thermostat sensor installations using
single-stage AC or HP.

VENTING

The furnace shall be connected to a listed factory built chimney or vent,
or a clay-tile lined masonry or concrete chimney. Venting into an unlined
masonry chimney or concrete chimney is prohibited.
When an existing Category I furnace is removed or replaced, the original
venting system, may no longer be sized to properly vent the attached
appliances. An improperly sized Category I venting system could cause
the formation of condensate in the furnace and vent, leakage of
condensate and combustion products, and spillage of combustion
products into the living space.
Vent system or vent connectors may need to be resized. Vent systems or
vent connectors must be sized to approach minimum size as determined
using appropriate table found in the current edition of NFPA 54/ANSI
Z223 .
General Venting Requirements
Follow all safety codes for proper vent sizing and installation
requirements, including local building codes, the National Fuel Gas
Code NFPA 54/ANSI Z223.1, Parts 12 and 13 in the United States, the
local building codes, and furnace and vent manufacturers' instructions.
These furnaces are design-certified as Category I furnaces in accordance
with ANSI Z21.47/CSA 2.3 and operate with a non-positive vent static
pressure to minimize the potential for vent gas leakage. Category I
furnaces operate with a flue loss not less than 17 percent to minimize the
potential for condensation in the venting system. These furnaces are
approved for common venting and multistory venting with other fan
assisted or draft hood equipped appliances in accordance with the
NFGC, the local building codes, and furnace and vent manufacturers'
instructions.
The following information and warning must be considered in addition
to the requirements defined in the NFPA 54/ANSI Z223.1.
WARNING
!
CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal injury or death.
Do not bypass the draft safeguard switch, as an unsafe condition could
exist which must be corrected.
1. If a vent (common or dedicated) becomes blocked, the furnace will
be shut off by the draft safeguard switch located on the vent elbow.
2. Two-stage furnaces require Type B vent connectors outside the
casing in all configurations. Single wall vent connector may be
used inside the furnace casing with the transition to Type B vent
outside the furnace casing. Size the connector so that the FAN-Min
vent connector capacity is equal to or lower than the low fire rate of
the furnace and the FAN-Max vent connector capacity is equal to or
higher than the furnace high fire rate.
3. Do not vent this Category I furnace into a single wall dedicated or
common vent. The dedicated or common vent is considered to be
the vertical portion of the vent system that terminates outdoors.
4. Vent connectors serving Category I furnaces shall not be connected
into any portion of a mechanical draft system operating under
positive pressure.
5. Do not vent this appliance with any solid fuel burning appliance.
6. Category I furnaces must be vented vertically or nearly vertically
unless equipped with a listed mechanical venter. See SIDEWALL
VENTING section.
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
7. Do not vent this appliance into an unlined masonry chimney. (Refer
to Chimney Inspection Chart,
CHIMNEY INSPECTION CHART
For additional requirements refer to the National Fuel Gas Code NFPA 54/ANSI Z223.1 and ANSI/NFPA 211
Chimneys, Fireplaces, Vents, and Solid Fuel Burning Appliances
Crown
Rebuild
condition:
Yes
crown.
Missing mortar
or brick?
No
Is chimney
No
property lined with
clay tile liner?
Yes
Repair
Is
No
liner or top seal
liner and top
or reline chimney as
seal in good
necessary.
condition?
Yes
Debris
Mortar
in cleanout?
Yes
or tile
Mortar, tile, metal vent,
debris?
fuel oil residue?
No
Remove metal vent
or liner.
Clay
Yes
tile misalignment,
missing sections,
gaps?
No
Is chimney
Condensate
lined with properly
drainage at bottom
sized, listed liner or
of chimney?
Type-B vent?
Yes
No
Chimney
Is chimney
exposed to
to be dedicated to
outdoors below
a single
roof line?
Yes
furnace?
No
Chimney is
acceptable for use.
Fig. 31 – Chimney Inspection Chart
Masonry Chimney Requirement
NOTE: These furnaces are CSA design-certified for use in exterior
tile-lined masonry chimneys with a factory accessory Chimney Adapter
Kit. Refer to the furnace rating plate for correct kit usage. The Chimney
Adapter Kits are for use with ONLY furnaces having a Chimney Adapter
Kit number marked on the furnace rating plate.
If a clay tile-lined masonry chimney is being used and it is exposed to
the outdoors below the roof line, relining might be required. Chimneys
shall conform to the Standard for Chimneys, Fireplaces, Vents, and Solid
Fuel Burning Appliances ANSI/NFPA 211 in the United States and must
be in good condition.
U.S.A. – Refer to Sections 13.1.8 and 13.2.20 of the NFPA 54/ANSI
Z223.1 or the authority having jurisdiction to determine whether relining
is required. If relining is required, use a properly sized listed metal liner,
Type-B vent, or a listed alternative venting design.
NOTE: See the NFPA 54/ANSI Z223.1 13.1.9 and 13.2.20 regarding
alternative venting design and the exception, which cover installations
such as our Chimney Adapter Kits which are listed for use with these
furnaces. See Product Data Sheet for accessory listing.
21
Fig.
31.
Reline
Repair
Yes
Remove mortar
and tile debris
No
Consult
Part B of
Not Suitable
chimney adapter venting
instructions for
No
application
suitability.
Line chimney with property
Suitable
sized, listed flexible metal
liner or Type-B vent per
Yes
Sizing Tables and liner or
Install chimney
vent manufacturer's
adapter per
Installation instructions.
instructions.
Not Suitable
Yes
Consult
Part C of
No
Suitable
chimney adapter venting
instructions for
application
suitability
Install chimney
adapter per
instructions.
NFGC Vent
A10133