Boiler block assembly
7.8.3

Inserting the flue gas baffle plates

In pre-assembled boilers, the flue gas baffles
are already fitted
B Remove the cardboard transport
protectors from the pre-assembled boiler.
B Take flue gas baffles from the crate and insert into the
flue gas passages as indicated by their inscription
(
Fig. 30 and Tab. 10).
Fig. 30 Flue gas baffle plates
Number
of flue
Number
gas
of boiler
baffle
sections
plates
5
4
6 – 7
4
8
4
9
4
Tab. 10
28
Length of
Installation
flue gas
directions on
baffle plate
the flue gas
in inches
baffle plate
(mm)
(
Fig. 30)
14-11/64
(360)
top right
17-21/64
top left
(440)
bottom right
14-11/64
bottom left
(360)
7-7/8 (200)
7.8.4

Fitting burner door panel

In the factory, the burner door is mounted with the hinges
on the right hand side (Fig. 31, [4 and 6]). For left-hand
closing, remove the hinges accordingly on the left-hand
side of the burner door.
B Screw the hinge pins (Fig. 31. [1 and 3]) to the front
boiler section with 2 M 12 x 50 machine screws in
each case. This is shown in Fig. 31 for the right-hand
closing version. For left-hand closing, secure hinge
pins accordingly on the left-hand side.
B Affix Ø 18 mm diameter GP cord in the front section
using adhesive. The sealant rope joint should be
located at the side (Fig. 31, [2]).
B Hook the burner door with the hinge lobes into the
hinge pins.