• If n084 is set to 1 or 2, the method to input the set point will be determined by the operation mode set
with n002 and the FI terminal will be used for feedback input. Set the FI input level with n043 to select
current feedback input or voltage feedback input to the Inverter.
Input terminal
p
Set point input
Frequency reference: n025 to n029
Feedback input
FI terminal: Frequency reference input (default-set to current frequency reference input)
n043

FI Input Level Selection

Setting range
0, 1
Set Values
Set value
0
Voltage input within a range from 0 to 10 V. Be sure to cut jumper wire J1.
1
Current input within a range from 4 to 20 mA.
Note Do not impose voltage on the Inverter without cutting jumper wire J1 if n043 is set to 0, otherwise
the input resistor of the Inverter will burn out.
D 200 V, 3.7 kW
Power input
n085

Feedback Adjustment Gain

Setting range
0.00 to 10.00
3-34
0 or 1 (Frequency reference: Digital
Operator)
Unit
Unit
Operation mode selection (n002)
2 or 3 (Frequency reference: Control
FV terminal: Voltage frequency reference
input
---
Description
Jumper wire
Motor output
Braking Resistor
Times
Chapter 3
circuit terminals)
Default setting
1
Control
circuit
terminals
Main circuit
terminals
Default setting
1.00

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents