Omron SYSDRIVE 3G3HV SERIES User Manual page 103

High-capacity general-purpose inverter
Hide thumbs Also See for SYSDRIVE 3G3HV SERIES:
Table of Contents

Advertisement

Preparing for Operation
Function
No.
Sequential in-
n039
put function
selection
Sequential out-
n040
put function
selection
n041
3-46
Name
Multi-function
0to 22: Same as n035
input 5 (S6)
25: Up/Down command
S5 will be used for the up command,
S6 will be used for the down com-
mand, and value set with n038 will be
ignored.
26: Not used. (Do not set.)
27: PID input characteristic selection
(ON: Deviation multiplied by –1)
Multi-function
0:
Error (ON: Error)
contact output
1:
Running
1 (MA-MB-MC)
2:
Frequency agreement
3:
Optional frequency agreement
4:
Optional frequency detection (ON:
Output frequency x n073)
5:
Optional frequency detection (ON:
Output frequency x n073)
6:
Overtorque (ON: Detected)
7:
Overtorque (OFF: Detected)
8:
Baseblock
9:
Operation mode (ON: Digital Opera-
tor/Frequency reference)
10: Inverter ready
11: Timer function output (Set with n077
and n078)
12: Error retrying
13: Inverter/Motor overload warning
14: Frequency reference loss (ON: Fre-
quency reference has dropped by
90% or more within 0.4 s)
15: Not used
16: PID feedback loss (Detecting method
can be set with n093 and n094)
17: Heating heat sink (ON: OH1)
Multi-function
Same as n040
contact output
2 (M1-M2)
Description
Chapter 3
Setting
Refer-
ence
range
page
2 to 27
3-18
[10]
0 to 17
3-74
[0]
0 to 17
3-74
[1]

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents