Jump Frequency 2; Jump Frequency Range; Total Operating Time Function Selection - Omron SYSDRIVE 3G3HV SERIES User Manual

High-capacity general-purpose inverter
Hide thumbs Also See for SYSDRIVE 3G3HV SERIES:
Table of Contents

Advertisement

Preparing for Operation
n059

Jump Frequency 2

Setting range
0.0 to 400.0
n060

Jump Frequency Range

Setting range
0.0 to 25.5
• The frequency jump prevents the Inverter from generating frequencies that make the mechanical sys-
tem resonate.
• The frequency jump can be used effectively to make dead bands for frequency references.
• Set with n058 and n059 the center values of jumping frequencies.
• The value set with n059 must be as large as or larger than the value set with n059, otherwise OPE6
(improper parameter setting) will result.
• Set with n060 a jump frequency width.
n061

Total Operating Time Function Selection

Setting range
0, 1
n062
Total Operating Time 1 (Rightmost 4 Digits)
Setting range
0 to 9,999
n063
Total Operating Time 2 (Leftmost 2 Digits)
Setting range
0 to 27
• Select with n061 whether to permit the Inverter to accumulate the power-ON time or operation time of
the Inverter.
Set Values (n061)
Set value
0
Accumulates power-ON time
1
Accumulates operation time
• Set with n062 and n063 the initial operation time of the Inverter. The accumulated operation time of the
Inverter can be obtained from the following.
Accumulated operation time (h) = n063 x 10,000 + n062
• The parameters n062 and n063 can be used to monitor the accumulated operation time of the Inverter.
• The maximum value of the accumulated operation time set with n062 and n063 is 279620 (h). When
the value of the accumulated operation time exceeds 279620, n062 and n063 will be set to 0.
3-84
Unit
Unit
Output
frequency
Unit
Unit
Unit
Hz
Default setting
Hz
Default setting
Frequency
reference
---
Default setting
h
Default setting
x 10,000 h
Default setting
Description
Chapter 3
0.0
1.0
1
0
0

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents