Preparing for Operation
n059
Jump Frequency 2
Setting range
0.0 to 400.0
n060
Jump Frequency Range
Setting range
0.0 to 25.5
• The frequency jump prevents the Inverter from generating frequencies that make the mechanical sys-
tem resonate.
• The frequency jump can be used effectively to make dead bands for frequency references.
• Set with n058 and n059 the center values of jumping frequencies.
• The value set with n059 must be as large as or larger than the value set with n059, otherwise OPE6
(improper parameter setting) will result.
• Set with n060 a jump frequency width.
n061
Total Operating Time Function Selection
Setting range
0, 1
n062
Total Operating Time 1 (Rightmost 4 Digits)
Setting range
0 to 9,999
n063
Total Operating Time 2 (Leftmost 2 Digits)
Setting range
0 to 27
• Select with n061 whether to permit the Inverter to accumulate the power-ON time or operation time of
the Inverter.
Set Values (n061)
Set value
0
Accumulates power-ON time
1
Accumulates operation time
• Set with n062 and n063 the initial operation time of the Inverter. The accumulated operation time of the
Inverter can be obtained from the following.
Accumulated operation time (h) = n063 x 10,000 + n062
• The parameters n062 and n063 can be used to monitor the accumulated operation time of the Inverter.
• The maximum value of the accumulated operation time set with n062 and n063 is 279620 (h). When
the value of the accumulated operation time exceeds 279620, n062 and n063 will be set to 0.
3-84