• Set instantaneous power failure compensation time in 1-s units.
• It is usually not necessary to change the default-set value.
n056

Number of Error Retries

Setting range
0 to 10
Caution
The Inverter may be damaged if the error retry function is used.
!
Caution
Given that the Inverter may be damaged if the error retry function is used, connect a
!
no-fuse breaker to the Inverter and program a sequence to interrupt the operation of
peripheral devices when the Inverter is error.
• The error retry function permits the Inverter to restart operation automatically, even if the Inverter is
error.
• Use the error retry function only in case the interruption of the operation of the mechanical system is
not desired, even if the Inverter may be damaged.
• The error retry function is valid for the following errors. A protection function of the Inverter will work if
the Inverter has any other error.
OC (Overcurrent)
OV (Main circuit overvoltage)
UV1 (Main circuit undervoltage)
GF (Ground fault)
RR (Control transistor overheat)
• The number of error retries counted will be cleared in the following cases.
When the Inverter is in normal operation for 10 minutes after an error retry.
When the Inverter receives error reset input after the Inverter detects an error with a protection
function.
When the Inverter is turned OFF and ON.
• To permit the Inverter to output an error retry signal, set the multi-function contact output parameter
used by the Inverter to 12.
n057

Selection of Error Output during Error Retry

Setting range
0, 1
• Select with n057 whether to permit the Inverter to turn ON error output while the Inverter is in error retry
operation.
• To permit the Inverter to turn ON error output while the Inverter is in error retry operation, set the multi-
function contact output parameter used by the Inverter to 0.
Set Values
Set value
0
Turns ON error output while error retry is performed.
1
Turns OFF error output while error retry is performed.
n058

Jump Frequency 1

Setting range
0.0 to 400.0
Unit
Times
Unit
---
Description
Unit
Hz
Chapter 3
Default setting
0
Default setting
0
Default setting
0.0
3-83