Frequency Detection Width - Omron SYSDRIVE 3G3HV SERIES User Manual

High-capacity general-purpose inverter
Hide thumbs Also See for SYSDRIVE 3G3HV SERIES:
Table of Contents

Advertisement

Preparing for Operation
Note 4. If n109 is set to 0.0, the slip compensation function will be disabled.
Note 5. Set the motor's rated frequency in n014.
n112
Operation Selection at Digital Operator interruption
Setting range
0, 1
Set Values
Set value
0
Digital Operator disconnection detection disabled
1
Digital Operator disconnection detection enabled
• This function can be used to detect a disconnection with the Digital Operator.
• When n112 is set to 1, if a disconnection with the Digital Operator is detected while the Inverter is run-
%pr
ning, an
error will be displayed and the motor will coast to a stop.
n113

Frequency detection width

Setting range
0.0 to 25.5
• Set the detection widths for frequency agreement (set value: 2), optional frequency agreement (set
value: 3), and optional frequency detection (set values: 4, 5) for multi-function inputs 1 to 5 (n035 to
n039).
Frequency agreement, optional frequency agreement:
Optional frequency detection:
n114
Operation Selection at Operation Mode Switching
(local/remote switching)
Setting range
0, 1
Set Values
Set value
0
Run signals that are input during mode switching are ignored. (Input run signals after switching
the mode.)
1
Run signals become effective immediately after switching to the Remote mode. (Operation after
the mode has switched will be determined by the status of the run signal at that time.)
Select whether or not to ignore run signals input while the operation mode is switched using the Operation Mode
Selection Key on the Digital Operator or with operation mode selection input from the multi-function inputs.
Note
If n114 is set to 1, when the operation mode changes the Inverter may start running immediately. Take steps
to ensure safety for such operation.
Unit
---
Description
Unit
Hz
Unit
---
Description
Default setting
Default setting
Detection width = Value set for n113
Release width = Twice value set for n113
Release width = Value set for n113
Default setting
Chapter 3
0
2.0
0
3-91

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents