Appendix
Function
No.
Overtorque
n074
detection
n075
n076
Timer function
n077
n078
Braking Resis-
n079
tor Unit over-
heating protec-
tion
I/O phase loss
n080
detection
n081
n082
Name
Overtorque
0: Inhibits Inverter from detecting overtor-
detection func-
que.
tion selection
1: Inverter will detect overtorque only dur-
ing speed agreement and continue run-
ning with warning after detection.
2: Running Inverter will detect overtorque
and continue running with warning after
detection.
3: Inverter will detect overtorque only dur-
ing speed agreement and turn OFF
output for safety when overtorque is
detected.
4: Running Inverter will always detect
overtorque and turn OFF output for
safety when overtorque is detected.
Overtorque
Set overtorque detection current in 1%
detection level
units based on rated output current of In-
verter as 100%.
Overtorque
Set overtorque detection time in 1-s units.
detection time
Overtorque will be detected if current larg-
er than value set with n075 flows for the
set time or more.
Timer function
Set time lag between moment timer func-
ON delay time
tion input turns ON and moment timer
function output turns ON.
Valid if multi-function input and multi-func-
tion contact output are set to timer func-
tion.
Timer function
Set time lag between the moment the tim-
OFF delay time
er function input turns OFF and the
moment the timer function output turns
OFF.
Valid if multi-function input and multi-func-
tion contact output are set to timer func-
tion.
Braking resistor
0: Inhibits overheating protection from
overheating
functioning.
protection
1: Permits overheating protection to func-
selection
tion.
Input open-
Set input phase loss detection level to per-
phase detec-
centage of main circuit DC voltage.
tion level
200-V class: 200 VDC as 100%
400-V class: 800 VDC as 100%
Input open-
Set input phase loss detection time.
phase detec-
Detection time = 1.28 x n n081
tion time
Inverter will detect input phase loss if volt-
age as large as or larger than value set
with n080 is imposed continuously for peri-
od exceeding set time.
Output open-
Set output phase loss detection level in
phase detec-
1% units based on rated output current of
tion level
Inverter as 100%.
Output phase loss detection will be invalid
if value is set to 0.
Description
Chapter 6
Setting
Refer-
ence
range
page
0 to 4
3-87
[0]
30 to
3-87
200
[160]
0.1 to
3-87
10.0
[0.1]
0.0 to
3-88
25.5
[0.0]
0.0 to
3-88
25.5
[0.0]
0, 1
3-88
[0]
1 to
3-89
100
[7]
2 to
3-89
255
[8]
0 to
3-89
100
[0]
6-15