Energy-Saving Control Settings; Energy-Saving Control Selection; Energy-Saving Coefficient K2 - Omron SYSDRIVE 3G3HV SERIES User Manual

High-capacity general-purpose inverter
Hide thumbs Also See for SYSDRIVE 3G3HV SERIES:
Table of Contents

Advertisement

Preparing for Operation
The most efficient input voltage imposed on the motor varies with the load factor of the motor. The In-
verter in energy-saving mode calculates the ideal output voltage and adjusts the ideal output voltage so
that the actual power supplied to the motor can be minimized.
H Energy-saving Control Settings
n095

Energy-saving Control Selection

Setting range
0, 1
Set Values
Set value
0
Inhibits the Inverter from performing energy-saving control.
1
Permits the Inverter to perform energy-saving control.
Note Set n095 to 1 so that the Inverter will perform energy-saving control.
n096

Energy-saving Coefficient K2

Setting range
0.00 to 655.0
Note The default-set value of n096 varies with the Inverter model.
Set Values
S Set the K2 value according to the capacity of the motor.
S The K2 value of each Inverter model is set to the following before shipping according to the maxi-
mum capacity of the motor that can be connected to the Inverter model.
3-26
Power
consumption
Load factor: 50%
Unit
Unit
Load factor: 100%
Motor voltage
---
Default setting
Description
---
Default setting
Chapter 3
0