Wiring Method; Reactor Effects - Omron SYSDRIVE 3G3HV SERIES User Manual

High-capacity general-purpose inverter
Hide thumbs Also See for SYSDRIVE 3G3HV SERIES:
Table of Contents

Advertisement

Installation

• Wiring Method

With DC Reactor
200 VAC (400 V)
Note Be sure to remove the short bar on terminals +1 and +2 before connecting the DC reactor.
With DC and AC Reactors
200 VAC (400 V)
Note Be sure to remove the short bar on terminals +1 and +2 before connecting the DC reactor.

• Reactor Effects

Harmonics are effectively suppressed when the DC reactor is used with the AC reactor as shown in
the following table.
Harmonic suppres-
pp
sion method
i
h d
No reactor
AC reactor
DC reactor
DC and AC reactors
2-30
AC reactor
(optional)
5th har-
7th har-
monic
monic
harmon-
65
41
8.5
38
14.5
7.4
30
13
8.4
28
9.1
7.2
DC reactor
(optional)
L1 (R)
T1 (U)
L2 (S)
T2 (V)
L3 (T)
T3 (W)
3G3HV
DC reactor
(optional)
L1 (R)
T1 (U)
L2 (S)
T2 (V)
L3 (T)
T3 (W)
3G3HV
Harmonic generation rate (%)
11th
13th
17th
harmon-
harmon-
ic
ic
ic
7.7
4.3
3.4
3.2
5
4.7
4.1
3.2
Chapter 2
19th
23th
harmon-
harmon-
ic
ic
monic
3.1
2.6
1.8
1.9
1.7
1.3
3.2
3.0
2.2
2.4
1.6
1.4
25th
har-

Hide quick links: