Preparing for Operation
H Group 2: n035 to n049
Function
No.
Sequential in-
n035
put function
selection
n036
n037
n038
Name
Multi-function
0:
Reverse rotation/Stop
input 1 (S2)
1:
Stop command (3-wire sequence
selection)
S3 will be used for forward/reverse
rotation command and value set with
n036 will be ignored.
2:
External error (NO contact: ON)
3:
External error (NC contact: ON)
4:
Error reset (ON: Valid)
5:
Operation mode selection (ON: Digital
Operator; OFF: n002)
6:
Not used
7:
Emergency stop
8:
Analog input selection (ON: Current
input through FI terminal; OFF: FV
terminal)
9:
Multi-step speed command 1
10: Multi-step speed command 2
11: Inching command
12: Acceleration/Deceleration time
switching command
13: External baseblock command (ON:
Valid)
14: External baseblock command (OFF:
Valid)
15: Speed search command from max.
frequency
16: Speed search command from set fre-
quency
17: Parameter set-inhibit (ON: Invalid)
18: Integral value of PID control reset
command
19: PID control invalidating command
(Set point used as frequency refer-
ence)
20: Timer function input (Set with n077
and n078)
21: Inverter overheat warning (ON: "OH3"
will be displayed)
22: Analog frequency sample hold
23: Power OFF stop input (NO contact)
24: Power OFF stop input (NC contact)
Multi-function
Same as n035
input 2 (S3)
Multi-function
Same as n035
input 3 (S4)
Multi-function
Same as n035
input 4 (S5)
Description
Chapter 3
Setting
Refer-
ence
range
page
0 to 24
3-17
[0]
2 to 24
3-17
[2]
2 to 24
3-17
[4]
2 to 24
3-17
[9]
3-45