VISTA-10SEa Installation and Setup Guide
Programming System Status and Restore Report Code Enables
( 60 – 68, 69 – 75)
Enter codes as follows:
1–9, 0, B, C, D, E, or F. Enter [#] + 10 for "0," [#] + 11 for "B," [#] + 12 for "C," [#] + 13 for
"D," [#] + 14 for "E," [#] + 15 for "F."
With ADEMCO Contact ID Reporting: Enter any digit (other than "0") in the first box,
to enable zone to report. This is an "enabling" code only and is disregarded in the actual
reporting to the central office. Entries in the second boxes will be ignored.
A "0" (not "# + 10") in the first box will disable the report.
Examples:
For Code Enable 30 (two digits), enter:
For Code Enable B0 (hexadecimal), enter:
13-4
Press 48 15-SECOND DIALER DELAY, BURGLARY
Enter 0 for no, or 1 for yes. Default is 0 (no delay).
Press 49 PERIODIC TEST REPORT
Select the desired Test report interval.
0 = none; 1 = 24 hours; 2 = weekly; 3 = 28 days. Default is 0
(none). Test Report Code entered in field 64 is sent.
Reports with Subscriber No.
Press 60 TROUBLE REPORT CODE ENABLE
This will be sent if a zone goes into trouble.
Press 61 BYPASS REPORT CODE ENABLE
This will be sent when a zone is manually bypassed.
Press 62 MAINS LOSS REPORT CODE ENABLE
Timing of this report is random with a delay of up to 48
minutes. The keypad response is about 6 seconds to display the
mains failure. The Restore report has a random delay of up to
about 12 minutes. If mains restores before the report goes out,
there is no mains Restore report.
Press 63 LOW BATTERY REPORT CODE ENABLE
This will be sent when a low-battery condition exists in the
system's standby battery.
NOTE: The system checks connection to the standby battery
every 3 minutes.
Press 64 TEST REPORT CODE ENABLE
This is sent periodically to test that the communicator and
phone lines are operational (frequency of report is selected in
field 51).
Press 65 OPEN REPORT CODE ENABLE
This is sent upon disarming of the system.
Press 66 ARM AWAY/STAY REPORT CODE ENABLES
This option allows for independent programming of AWAY and
STAY reports.
Press 67 RF XMTR. LOW BATTERY REPORT CODE ENABLE
This is sent in the event that a wireless transmitter low-
battery condition exists.
3
0
#+11
0