ADEMCO N7227V5 Installation And Setup Manual

Vista security system installation and setup guide
Hide thumbs Also See for Ademco N7227V5:
Table of Contents

Advertisement

N7227V5 10/00

AWAY
NO AC
STAY
CHIME
ARMED
INSTANT
BAT
ALARM
BYPASS
CHECK
READY
FIRE
NOT READY
OFF
AWAY
STAY
1
2
3
MAX
TEST
BYPASS
4
5
6
INSTANT
CODE
CHIME
7
8
9
READY
*
0
#
PANIC
®

Advertisement

Table of Contents
loading

Summary of Contents for ADEMCO Ademco N7227V5

  • Page 1 N7227V5 10/00 AWAY NO AC STAY CHIME ARMED INSTANT ALARM BYPASS CHECK READY FIRE NOT READY AWAY STAY TEST BYPASS INSTANT CODE CHIME READY PANIC ®...
  • Page 2: Recommendations For Proper Protection

    RECOMMENDATIONS FOR PROPER PROTECTION The following recommendations for the location of fire and burglary detection devices help provide proper coverage for the protected premises. Recommendations for Smoke and Heat Detectors With regard to the number and placement of smoke/heat detectors, we subscribe to the recommendations contained in the National Fire Protection Association's (NFPA) Standard #72 noted below.
  • Page 3: Table Of Contents

    SECTION 1. Introduction... 1–1 Description ...1-1 Features...1-1 SECTION 2. Installing the Control ... 2–1 Mounting the Cabinet ...2-1 Installing the Lock (if used) ...2-1 Mounting the Control's Circuit Board Alone in the Cabinet ...2-2 Mounting the Control and RF Receiver Circuit Boards Together...2-2 Standard Phone Line Connections ...2-3 SECTION 3.
  • Page 4 SECTION 11. Final Power-Up ... 11–1 Earth Ground Connections ...11-1 Wiring the AC Transformer ...11-1 AC Power-Up ...11-2 Calculating the Battery Size Needed ...11-2 Connecting the Backup Battery...11-3 SECTION 12. Mechanics of Programming ... 12–1 About Programming ...12-1 Entering the Program Mode ...12-1 SECTION 13.
  • Page 5: Introduction

    In This Section Description Description The VISTA–10SE is a control that supports up to 22 hardwired and wireless zones, plus remote keypads. Features Basic Hardwired Zones Provides 6 basic hardwired zones having the following characteristics: Zones 1-6 response time is 300–500 milliseconds.
  • Page 6 VISTA-10SE Installation and Setup Guide Security Codes • One Master code for entire system (User 2). Installer code is User 1. • 4 secondary user codes (Users 3–6). • One duress code (User 8). Duress Code: An emergency code that, when used to disarm or arm the system, will send a silent duress message to the central station .
  • Page 7 Alarm Output Provides a 12VDC, 2 AMP output that can drive the compatible sounders listed in the EXTERNAL SOUNDERS section (assumes a fully charged battery is connected). Steady output for burglary/panic, or temporal pulse sounding output for fire notification, as required by UL. Uses current-limiting circuitry for protection.
  • Page 8 VISTA-10SE Installation and Setup Guide...
  • Page 9: Installing The Control

    In This Section Mounting the Cabinet Installing the Lock Mounting the Control's Circuit Board Alone in the Cabinet Mounting the Cabinet Mount the control cabinet to a sturdy wall using fasteners or anchors (not supplied), in a clean, dry area that is not readily accessible to the general public. Four mounting holes are provided at the back of the cabinet for this purpose.
  • Page 10: Mounting The Control's Circuit Board Alone In The Cabinet

    VISTA-10SE Installation and Setup Guide Mounting the Control's Circuit Board Alone in the Cabinet To mount the circuit board alone in the cabinet, follow these steps: 1. Hang two mounting clips* (provided) on the raised cabinet tabs (see Detail B in Figure 2 below).
  • Page 11: Standard Phone Line Connections

    BOARD SUPPORTING SLOTS MOUNTING CLIP MOUNTING CLIP CABINET ANTENNA AND GROUNDING LUG INSTALLATION Figure 3. Mounting the PC Board and RF Receiver Together in the Cabinet Standard Phone Line Connections The wiring connections shown here are not applicable if a 4285/4286 VIP Module is used. Refer to the 4285/4286 VIP MODULE section for information regarding phone line connections, which are different than those shown here.
  • Page 12 VISTA-10SE Installation and Setup Guide INCOMING TELECOM LINE HANDSET TERMINALS ON CONTROL EARTH GROUND INCOMING TELECOM LINE PLUG RJ31X PREMISES JACK RING PHONES DIRECT CONNECT CORD V10SE-024-V0 Figure 4. Standard Telephone Line Connections...
  • Page 13: Keypads That May Be Used

    In This Section Keypads That May Be Used Wiring to the Keypads Mounting the Keypads This section lists the wired keypads that may be used and provides instructions for wiring and mounting the keypads. A preliminary checkout procedure is also provided to ensure that the connected keypads are functioning properly in the system.
  • Page 14: Mounting The Keypads

    VISTA-10SE Installation and Setup Guide Wiring Run Chart for Devices* Drawing Aux Power From the Control (12V+ & 12V–) TOTAL CURRENT DRAWN BY ALL DEVICES CONNECTED TO A SINGLE WIRE RUN Wire Size 50mA or less 750 ft (228.6m) 1300 ft (396m) 1500 ft (457m) Includes keypads, RF receivers, relay units, and 4285/4286 VIP Modules.
  • Page 15: Preliminary Checkout Procedure

    Keypads powered from supplies that do not have a backup battery will not function when AC power is lost. Therefore, be sure to power at least one keypad from the Control's auxiliary power output. Connect the additional keypads as shown in Figure 6, using the keypad wire colors shown. Be sure to observe the current ratings for the power supply used.
  • Page 16 VISTA-10SE Installation and Setup Guide If the “Ready” message is not displayed on any of the keypads in the system, or a “Not Ready” message is displayed, check the keypad wiring connections, and make sure each of the 6 basic hardwired zones has a 1000 ohm resistor connected across its terminals.
  • Page 17: Basic Hardwired Zones 1-6

    To wire burglary and panic devices to zones 1-6, perform the following steps, referring to Figure 17. VISTA-10SE Summary of Connections on the inside back cover of this manual. 1. Connect sensors/contacts to the hardwired zone terminals (8 through 16). See the Summary of Connections diagram.
  • Page 18: Programming Hardwired Zones

    VISTA-10SE Installation and Setup Guide 3. To meet NFPA 72 requirements, you must use a supervisory module to supervise power (e.g., System Sensor No. A77-716B Relay module). AUX PWR OUTPUT TERMINALS TO HI SIDE OF ZONE 5 DETECTOR TO LO SIDE Figure 7.
  • Page 19: Wireless Expansion (5800 System)

    Installing the 5800TM Module About Wireless Expansion The VISTA-10SE supports up to 16 wireless zones that may be used exclusively or in addition to hardwired zones 1 through 6. The receiver detects signals from wireless transmitters within a nominal range of 200 feet.
  • Page 20: Installing The 5881/5882 Receiver

    VISTA-10SE Installation and Setup Guide Installing the 5881/5882 Receiver RF System Installation Advisories Follow the guidelines below when installing the RF receiver. (Disregard if the receiver is mounted in the control cabinet.) Place the RF receiver in a high, centrally located area for best reception.
  • Page 21: Installing The 5800Tm Module

    Connect the 5800TM to the control panel’s keypad connection terminals, using the supplied connector with flying leads, as follows: Do not cut any of the jumpers on the 5800TM when using it with the VISTA-10SE. For additional information, refer to the 5800TM’s instructions.
  • Page 22 12-hour period, the “missing” transmitter number(s) and the message CHECK is displayed. In accordance with ULC standards, the RF supervision period for the VISTA-10SE is three hours for fire zones (Zone Type 9) and 12 hours for all other zone types.
  • Page 23: Series Transmitters Table

    The wireless system can identify a true low-battery situation, thus allowing the dealer or user of the system time to arrange a change of battery and maintain protection for that point within the system. Some transmitters (e.g., 5802, 5802CP, and 5804) contain long-life but nonreplaceable batteries, and no battery installation is required.
  • Page 24: Installing 5800 Series Transmitters

    VISTA-10SE Installation and Setup Guide 5800 Series Transmitters Table ( Model Description 5817 Multi-Point Universal Transmitter (cont'd.) (cont'd.) 5818 Recessed Magnetic Contact Transmitter 5819 Shock Processor Transmitter 5819 5819 5849 Glassbreak 5850 Detector/Transmitter 5852 5890 PIR Detector/ 5890P1 Transmitter When “enrolling” a transmitter’s ID code(s), any PIR in the vicinity that is not being enrolled should be covered with a cloth, tissue, etc.
  • Page 25: Relay Output Devices

    In This Section Relay Device Basics 4204 Relay Modules Relay Device Basics Relays are programmable switches that can be used to perform many different functions. They can be used to turn lights on and off, control sounders, or for status indications. In this system, each relay must be programmed as to how to act (ACTION), when to activate (START), and when to deactivate (STOP).
  • Page 26: Programming Options

    COVER TAMPER (REED) SWITCH Programming Options In the VISTA-10SE, each device must be programmed as to how to act (ACTION), when to activate (START), and when to de-activate (STOP). Refer to the programming procedures for 80 and 81 interactive modes that are provided in the MECHANICS of PROGRAMMING, OUTPUT DEVICE PROGRAMMING, and ZONE LISTS sections for specific programming details.
  • Page 27: 4285 And 4286 Vip Module

    Installing the (Voice Interactive Phone) Module General Information The 4285/4286 VIP Module is an add-on accessory for the VISTA–10SE that permits access to the security system via a TouchTone phone (either on premises or by a call-in when away). The VIP Module can announce many of the same words that would normally be displayed on an alpha keypad under the same system conditions.
  • Page 28 VISTA-10SE Installation and Setup Guide VIP Module Wiring The VIP Module is wired between the control panel and the premises handset(s). It listens for touch-tones on the phone line and reports them to the control panel. During on-premises phone access, it powers the premises phones; during off-premises phone access, it seizes the line from the premises phones and any answering machines.
  • Page 29 4285/4286 VIP Module WIRING NOTES: 1. Wire the VIP Module exactly as shown, using a direct-connect cord and RJ31X jack. 2. If you do no hear tones when pressing keys after accessing the security system via an on-premises phone, try reversing the pair of wires connected to terminals 3 and 4 on the VIP Module and the pair of wires connected to terminals 17 and 18 on the control.
  • Page 30: Programming The Control For Phone Access

    VISTA-10SE Installation and Setup Guide Programming the Control for Phone Access To program the control for phone access using the 4285/4286 VIP Module, you must assign a VIP Module access code ( 26) and ring detection count ( 95). Also, you may optionally select words and/or form custom words that would be displayed on the keypad.
  • Page 31: External Sounders

    Indoor Piezo Sounder For UL installations, use only UL Listed sounding devices mounted indoors. NFPA Requirements The VISTA-10SE complies with NFPA requirements for temporal pulse sounding of fire notification appliances. Temporal pulse sounding for a fire alarm consists of the following: 3 pulses –...
  • Page 32: Sounder Connections And Power

    VISTA-10SE Installation and Setup Guide Sounder Connections and Power The VISTA-10SE provides a 12VDC output, which can power external alarm sounders, bells, or sirens (see table of compatible sounders on a previous page). This output activates a sounder when an alarm occurs.
  • Page 33: Long-Range Radio

    In This Section About Long-Range Radio Wiring Connections About Long-Range Radio If output to Long-Range Radio (LRR) is selected, all messages that are programmed to go to the primary telephone line receiver are also sent to any LRR that can operate in ECP mode. These messages (by telephone or radio) are sent in Contact ID format (not affected by entry in field 46).
  • Page 34: Dynamic Signaling Feature

    VISTA-10SE Installation and Setup Guide Dynamic Signaling Feature This VISTA-10SE control panel features Dynamic Signaling Delay (DSD) and Dynamic Signaling Priority (DSP) message reporting when Long-Range Radio is used. These message outputs are accessed through data field 93. The Dynamic Signaling feature is designed to reduce the number of redundant reports sent to the central station.
  • Page 35: Section 10. Audio Alarm Verification (Aav) Unit

    Audio Alarm Verification (AAV) Unit In This Section About Audio Alarm Verification About Audio Alarm Verification An Audio Alarm Verification (AAV) module, such as the Eagle 1250, is an add-on accessory that permits voice dialog between an operator at a central station and a person at the alarm installation, for the purpose of alarm verification.
  • Page 36 VISTA-10SE Installation and Setup Guide EAGLE SUPPLIED CABLE CONTROL/ DIALER HEADER DIP Switch • • • • • EAGLE 1250 Figure 15. Connection of AAV Unit When Not Using a 4285 or 4286 VIP Module EAGLE SUPPLIED CABLE CONTROL/ DIALER HEADER DIP Switch •...
  • Page 37: Section 11. Final Power-Up

    In This Section Earth Ground Connections Wiring the AC Transformer AC Power-Up Earth Ground Connections The designated earth ground terminal (21) must be terminated in a good earth ground for the lightning transient protective devices in this product to be effective. The following are examples of good earth grounds available at most installations: Metal Cold Water Pipe: Use a non-corrosive metal strap (copper is recommended) firmly secured to the pipe to which...
  • Page 38: Ac Power-Up

    VISTA-10SE Installation and Setup Guide AC Power-Up To turn on AC power, perform the following steps: 1. Plug the 1321/1321CN into a 24-hour, unswitched 120VAC outlet. Following power-up, one of the following is displayed on the keypad: AC, dI (disabled);...
  • Page 39: Connecting The Backup Battery

    Connecting the Backup Battery In the event of an AC power loss, the control panel is supported by a backup, rechargeable Sealed Lead Acid battery. The range of battery sizes recommended are: 12VDC; 4AH- 17.2AH. See "Calculating the Battery Size Needed" earlier in this section. The battery is installed in the control cabinet.
  • Page 40 VISTA-10SE Installation and Setup Guide 11-4...
  • Page 41: Section 12. Mechanics Of Programming

    In This Section About Programming Entering Program Mode Programming a Data Field Reviewing a Data Field/Erasing an Entry About Programming This section provides information on how programming is performed in this system. It will enable you to understand how to enter and exit the Programming mode, and how to program the data fields and the user-friendly Interactive Menu modes ( 56, 58, 80, 81, 82).
  • Page 42 VISTA-10SE Installation and Setup Guide If a different Installer code is subsequently programmed, use it instead of 4111 to gain access to the Programming mode. When you enter the Program mode, data field 20 is displayed (this is the first data field in the system).
  • Page 43: Section 13. Zone Response Type Definitions

    Zone Response Type Definitions In This Section Zone Type Definitions Zone Type Definitions You must assign to each zone a zone type that defines the way in which the system responds to faults in that zone. Zone types are defined below. Zone type 00 is used to program a zone that is not used.
  • Page 44 VISTA-10SE Installation and Setup Guide Type 05 Trouble by Day/ Alarm by Night Type 06 24-hour Silent Alarm Type 07 24-hour Audible Alarm Type 08 24-hour Auxiliary Alarm Type 09 Supervised Fire 5806/5807/5808 01000-020-V0 Type 10 Interior w/Delay 13-2 Zone type 05 is usually assigned to a zone that contains foil-protected doors or windows;...
  • Page 45 Zone type 20 is a special-purpose zone type used with 5800 Series wireless Type 20 pushbutton transmitters. Arm–STAY Zone Characteristics: Exit delay regardless of the arming mode selected. System is armed in the STAY mode when the zone is activated. Zone number is sent to the central station as a user number when arming or disarming.
  • Page 46 VISTA-10SE Installation and Setup Guide 13-4...
  • Page 47: Section 14. Data Field Descriptions

    In This Section Descriptions of System Data Fields NOTE: The following program field must be programmed before doing any zone programming: 22 RF SYSTEM Descriptions of System Data Fields The blank programming form (separate insert) should be used to record the data for this installation.
  • Page 48 VISTA-10SE Installation and Setup Guide ZONE SOUNDS AND TIMING ( 28– 39) 14-2 VOICE (PHONE) MODULE ACCESS CODE The use of a 4285 or 4286 VIP (Phone) Module requires a 2-digit code. Enter a 2-digit phone access code as follows: For first digit, enter any digit from 1 to 9;...
  • Page 49 DIALER PROGRAMMING ( 40– 50) Fields 40, 41, 42: Enter up to the number of digits shown. Do not fill unused spaces. Enter 0–9, # + 11 for # + 12 for # # + 13 for a pause (2.5 secs) AUDIBLE EXIT WARNING If enabled, this field provides exit warning sound when armed AWAY or MAXIMUM.
  • Page 50 VISTA-10SE Installation and Setup Guide For an explanation of these formats, see the SYSTEM COMMUNICATION section. Can only be used if the Primary reporting format is ADEMCO Contact If reporting to a Pager, choose from 6, 7, 8, or 9, as desired.
  • Page 51 A 10-digit code is sent to the pager that is coded in the following format: 4-digit Subscriber No. SSSS–EEE–NNN 3-digit User or Zone No. (as entered in field 43) 3-Digit Event Code (EEE), as follows: 911 = Alarm (NNN = Zone No.) 001 = Open, System disarmed (NNN = User No.) 002 = Close, System armed ( NNN = User No.) 811 = Trouble ( NNN = Zone No.)
  • Page 52 VISTA-10SE Installation and Setup Guide TO PROGRAM SYSTEM STATUS AND RESTORE REPORT CODES ( 60 – 68, 70 – 75) 14-6 ZONE 3 RESPONSE TIME TO OPEN (1-Digit Entry) 0 = 400mS nominal; 1 = 10mS nominal. ZONE ASSIGNMENT/ALARM REPORT CODES...
  • Page 53 SYSTEM STATUS TROUBLE REPORT CODE (See box above.) REPORT CODES ( 60 – 68) BYPASS REPORT CODE (See box above.) AC LOSS REPORT CODE (See box above.) Reports with Subscriber No. Timing of this report is random with up to a 48-minute delay. The Restore Report has a random delay of up to about 12 minutes.
  • Page 54 VISTA-10SE Installation and Setup Guide RESTORE REPORT CODES ( 70 – 75) 14-8 ALARM RESTORE REPORT CODE (See box on previous page). For expanded or 4+2 reporting, a 2nd digit is automatically sent, and is the same as the 2nd digit of the zone Alarm Report code programmed in field 56.
  • Page 55 DYNAMIC SIGNALING DELAY (DSD) (1st entry) This field enables you to select the time the panel should wait for acknowledgment from the first reporting destination before it attempts to send a message to the second destination. Delays can be selected from 0 to 225 seconds, in 15-second increments.
  • Page 56 VISTA-10SE Installation and Setup Guide Important Note: If “15” is entered in field and a 4285/4286 VIP Module is included in the installation, you should note the following: When calling in from an off-premises phone (to receive a status report or execute a command), the user should make the initial call, allow 1 to 3 rings only, and hang up.
  • Page 57: Section 15. Zone Programming

    In This Section About Zone Programming 56 Zone Programming Mode Procedures 58 Expert Programming Mode Procedures About Zone Programming 56 Zone Programming and 58 Expert Programming are Interactive Menu modes that are used to program zone numbers, alarm codes, and report codes, and to identify the type of input device.
  • Page 58 VISTA-10SE Installation and Setup Guide È Zone Number 10 Zone Type Perimeter Zone Type 10 Report Code 1st 01 2nd 00 Note that report codes are defaulted to 10 for use with CID reporting. 10 INPUT TYPE RF TRANS 15–2 Zone Type (ZT): Enter the Zone Type response (or change it, if necessary).
  • Page 59 Serial number Entry and Loop Number Entry. 10 INPUT S/N: Used only when enrolling wireless transmitters. A 0 2 2 - 4 0 6 4 a. Transmit an open and close sequence. If using a button-type Note: The [A] and [B] keys transmitter, press and release the button;...
  • Page 60: Series Transmitter Input Loop Identification

    VISTA-10SE Installation and Setup Guide 5800 Series Transmitter Input Loop Identification All of the transmitters illustrated on this page have one or more unique factory-assigned input (loop) ID codes. Each of the input loops requires its own programming zone (e.g., a 5804's four input loops require four programming zones).
  • Page 61 Confirmation Option: This prompt appears only if you answered XMIT TO CONFIRM Yes to the first prompt in this section. PRESS TO SKIP he system enters a confirmation mode so that the operation of the actual programmed input can be confirmed. Activate the loop input or button that corresponds to this zone.
  • Page 62 VISTA-10SE Installation and Setup Guide 58 Expert Programming Mode Procedures Enter the Program mode and follow the step-by-step instructions below. NOTE: Before proceeding, you must program field 22 (RF System) as required. SET TO CONFIRM? 0 = NO 1 = YES 0...
  • Page 63 Serial Number entry and Loop Number entry. 10 INPUT S/N: Used only when enrolling wireless transmitters. A 0 2 2 - 4 0 6 4 a. Transmit an open and close sequence. If you are using a button- Note: The [A] and [B] keys type transmitter, press and release the button;...
  • Page 64 VISTA-10SE Installation and Setup Guide To Remove a Zone To either temporarily or permanently remove a zone from the 5800 system: 1. Enter the programming mode: Key Installer Code + 8 + 0 and press 56. S E T T O C O N F I R M ? 0 = N O 1 = Y E S E n t e r Z n N u m .
  • Page 65 If you want to replace the serial number continue to step 4; otherwise, skip to step 7. A display for the new transmitter number appears. Key the transmitter. The new transmitter serial number replaces the X’s in the display. The new summary display appears with a small “s” next to the loop number to indicate that the new transmitter serial number has been learned.
  • Page 66 VISTA-10SE Installation and Setup Guide XMIT TO CONFIRM PRESS TO SKIP K e y d A 0 2 2 - 4 0 6 3 – R c v d A 0 2 2 - 4 0 6 4 NOTE: Following the successful enrollment of each wireless device, remove ONE of the serial number labels from the device and affix it in the appropriate column on the ENROLLED TRANSMITTERS worksheet of the Programming Form.
  • Page 67 YOU MUST PROGRAM THIS BUTTON LOOP 4 ENROLL AS "BR" 5804 Wireless Key Transmitter For 5804 TEMPLATE 1 Loop Function No Response Disarm Arm AWAY No Response TEMPLATE 2 Loop Function No Response Disarm Arm AWAY Arm STAY TEMPLATE 3 Loop Function 24-hour Panic...
  • Page 68 VISTA-10SE Installation and Setup Guide 15–12...
  • Page 69: Section 16. Output Device Programming

    In This Section Programming Options Defined Programming Options Defined The following definitions will help you understand the programming of output devices when using 80 (this section) and 81 (the Zone List section that follows). The options used to start and stop these devices are described below, followed by the actual screen prompts and available entries.
  • Page 70 VISTA-10SE Installation and Setup Guide 2. ZONE LIST (ZL) is a group of zones to which the “EVENT” applies in order 3. ZONE TYPE/SYSTEM OPERATION (ZT). If a System Operation, such STOP (STP): The "STOP" programming determines when and under what conditions the 1.
  • Page 71 Programming Output Devices 1. With at least one 2-line alpha keypad (6139) connected to the keypad 2. Enter the programming mode by keying the following on the alpha keypad: 3. Press 80. Note that this is an Interactive Menu Programming mode. It is Output Device Displays Enter Relay No.
  • Page 72 VISTA-10SE Installation and Setup Guide 02 Start: Zn List No List 02 Start: Zn Typ Not Used 02 Stop: Zn List No List 02 Stop: Zn Typ Not Used 02 A EV ZL ZT STT 0 0 0 00 A EV ZL ZT STP –...
  • Page 73: Section 17. Zone Lists

    In This Section About Zone List Menu Mode About Zone List Menu Mode Zone List Menu mode is used to program zone lists for output devices (programmed in 80 Menu mode). Refer to the Programming Form worksheet ( 81) that programs the Zone Lists for Output Devices.
  • Page 74 VISTA-10SE Installation and Setup Guide 17–2 Notes: • Any list may include any or all of the system's zone numbers. • A zone list can be assigned to more than one output relay. • If you only want to review what has been programmed previously, press #81.
  • Page 75: Section 18. Alpha Descriptor Programming

    (on a following page) shown in boldface type. The VIP Module will not provide annunciation of the other words. If a VIP Module is added to an existing VISTA–10SE system, you must re-program the alpha descriptors presently in the system, selecting from those words shown in boldface type in the Alpha Vocabulary list.
  • Page 76 VISTA-10SE Installation and Setup Guide P r o g r a m A l p h a ? 0 = N o , 1 = Y e s C u s t o m W o r d s ?
  • Page 77 Z N 0 1 B A C K D O O R A Flashing Cursor if “6” is pressed (system ready for next word). Z N 0 1 B A C K D O O R A l p h a P g m Adding Custom Words (will not be annunciated by the 4285/4286 VIP Module) 9.
  • Page 78 VISTA-10SE Installation and Setup Guide 6. Press the [8] key to save the custom word(s) and return to the "CUSTOM 18-4 Repeat steps 3 and 4 to create the desired word(s). Note that the [4] key can be used to move the cursor to the left. Use the [6] key to make a space between characters.
  • Page 79 NOTE: Some rarely used words appearing in previously published lists have been deleted from the list below. Use only this list for selecting zone descriptors. (Word Space) • 057 • 001 • 059 • 002 ALARM • 060 ALLEY AMBUSH •...
  • Page 80 VISTA-10SE Installation and Setup Guide 18-6...
  • Page 81: Section 19. Remote Programming And Control (Downloading)

    In This Section About Remote Programming About Remote Programming VISTA–10SE Personal Computer (PC) a modem, and ADEMCO’s Compass Windows downloading software. Programming the control from a remote location is protected against compromise by someone attempting to defeat the system, using multi-levels of security protection: 1.
  • Page 82 VISTA-10SE Installation and Setup Guide Equipment Required At the premises: VISTA–10SE and keypad. At the installer's office/home: An IBM PC-compatible computer. Either a SMARTMODEM 1200 (Level 1.2 or higher external or Level 1.1 or higher [with 4 position DIP switch] internal style), or an Optima 24 Plus FAX96 Modem.
  • Page 83: Section 20. System Communication

    In This Section Panel Communication with Central Station Report Code Formats Panel Communication with Central Station This section provides an explanation of formats this system accommodates for reporting alarms and other system conditions to the central station. The process of a successful transmission consists of both the method of communication between the control panel and the central station receiver;...
  • Page 84: Table Of Contact Id Event Codes

    VISTA-10SE Installation and Setup Guide The following describes each format in greater detail. 3+1 and 4+1 Standard Formats 3+1 and 4+1 Expanded Formats 4+2 Format ADEMCO Contact ID Reporting Format ADEMCO Contact ID Reporting takes the following format: CCCC Q EEE GG ZZZ...
  • Page 85: Section 21. System Operation

    In This Section Security Codes Keypad Functions 4285/4286 VIP Module Security Codes Installer Code The installer programs the 4-digit Installer Code initially as part of the programming procedure. The factory default Installer Code is "4-1-1-1", but may be changed in field 20. NOTE: The Installer Code is defined as User 1.
  • Page 86: Keypad Functions

    VISTA-10SE Installation and Setup Guide Duress Code This feature is intended for use when you are forced to disarm or arm the system under threat. When used, the system will act normally, but can silently notify the central station of your situation, if that service has been provided.
  • Page 87 Arming INSTANT ... Enter code + INSTANT [7]. Arming MAXIMUM... Enter code + MAXIMUM [4]. Quick Arming ... Simply press [#] key in place of code, then press (if enabled) Disarming... Enter code + OFF [1]. Bypassing Zones ... Enter code + BYPASS [6] + zone number(s). Forced (Quick) Bypass ...
  • Page 88: Trouble Conditions

    VISTA-10SE Installation and Setup Guide 4285/4286 VIP Module (if used) Refer to the separate instructions supplied with the VIP Module for information concerning its operating procedures. Relay Outputs (if used) If relay outputs are used, two keypad entries available to the user are included among the system operation choices (34 and 35) that may be programmed (see the OUTPUT DEVICE PROGRAMMING section).
  • Page 89 A display of BAT (on fixed-word keypads) or SYSTEM LO BAT (on alpha keypads) with no zone number indicates that the system's main standby battery is weak. A display of "BAT" (on fixed-word keypads) or “LO BAT” (on alpha keypads) with a zone number and a once per minute "beeping"...
  • Page 90 VISTA-10SE Installation and Setup Guide 21-6...
  • Page 91: Section 22. Testing The System

    In This Section Test Procedures Transmitter Sniffer Mode Test Procedures After installation is completed, the system should be carefully tested, as follows: 1. With the system in the disarmed state, check that all zones are intact. If a NOT READY message is displayed, press the [ ] key to display the faulted zone(s).
  • Page 92 VISTA-10SE Installation and Setup Guide If a key (or key pair) has been programmed for fire, the keypad and external sounder will emit an interrupted alarm sound, and ALARM, FIRE and zone number will be displayed. Silence alarms by entering the security code and pressing [OFF] key.
  • Page 93: Section 23. Specifications & Accessories

    In This Section Specifications Specifications VISTA 10SE Security Control 1. Physical: 12-1/2" W x 14-1/2" H x 3" D (318mm x 368mm x 76mm) 2. Electrical: VOLTAGE INPUT: 16.5VAC from plug-in 25VA transformer, ADEMCO No. 1321 RECHARGEABLE BACKUP BATTERY: 12VDC, 4AH-17.2AH (Sealed Lead Acid).
  • Page 94: Accessories (Compatible Devices)

    VISTA-10SE Installation and Setup Guide Accessories (Compatible Devices) No. 1321 No. 1321CN Sounders ADEMCO AB-12M 10” Motorized Bell & Box ADEMCO 1011BE12M 10” Motorized Bell & Box ADEMCO 702 Outdoor Siren ADEMCO 719 2-Channel Siren ADEMCO 747 Indoor Siren ADEMCO 747UL...
  • Page 95: Appendix A Regulatory Agency Statements

    FEDERAL COMMUNICATIONS COMMISSION (FCC) PART 15 STATEMENT This equipment has been tested to FCC requirements and has been found acceptable for use. The FCC requires the following statement for your information: This equipment generates and uses radio frequency energy and if not installed and used properly, that is, in strict accordance with the manufacturer's instructions, may cause interference to radio and television reception.
  • Page 96 VISTA-10SE Installation and Setup Guide 1. This is a "Grade A" residential system. 2. The 4285/4286 VIP Module and 7720PLUS or 7820 Long-Range Radios have not been UL tested and cannot, therefore, be used in a UL installation. 3. The Entry Delay (field 38) cannot be greater than 45 seconds for UL installations.
  • Page 97: Appendix B Limitations And Warranties

    THE LIMITATIONS OF THIS ALARM SYSTEM While this System is an advanced design security system, it does not offer guaranteed protection against burglary, fire or other emergency. Any alarm system, whether commercial or residential, is subject to compromise or failure to warn for a variety of reasons.
  • Page 98 VISTA-10SE Installation and Setup Guide Alarm Device Manufacturing Company, a Division of Pittway Corporation, and its divisions, subsidiaries and affiliates (“Seller”), 165 Eileen Way, Syosset, New York 11791, warrants its products to be in conformance with its own plans and specifications and to be free from...
  • Page 99 BATTERY FUSE (e.g. ADEMCO No. 90-12) 24 HR BATTERY STANDBY REQUIRED FOR REPLACEMENT FOR FIRE INSTALLATIONS. USE 12V, USE SAME VALUE 17.2AH BATTERY FOR 500 mA AUX POWER. SEE INSTRUCTIONS. BATTERY CAPACITY FOR EMERGENCY BURGLARY STANDBY USE AT LEAST 4 HOURS.
  • Page 100 165 Eileen Way, Syosset, New York 11791 Copyright © 2000 PITTWAY CORPORATION N7227V5 10/00...

This manual is also suitable for:

Ademco vista-10seVista-10se

Table of Contents