Automatic Test Report; Report Expiry Time; Remote Pc Settings - Bosch AMAX panel 4000 Installation Manual

Icp-amax4-p1 / icp-amax4-p2-en / icp-amax-p3-en
Hide thumbs Also See for AMAX panel 4000:
Table of Contents

Advertisement

44
en | Settings
For more information about test report time programming, see Test Report Time. For more
information about date and time settings, see Date and Time Settings.
7.1.7

Automatic Test Report

The test report is divided into two types: periodic and regular daily report.
7.1.8

Report Expiry Time

If the report expiry time expires and the report path has not been connected, the report will
be lost and will not be sent. It can be maintained for 1 to 255 minutes. The system is
defaulted to 000, indicating that the report has been tried to send without limit in expiry time.
7.1.9

Remote PC Settings

By means of running Remote Programming Software (RPS) on a remote PC (RPC), the alarm
control panel can be remotely programming or controlled, including uploading/downloading
programming parameters, remote arming/disarming of each area, enabling/disabling the alarm
siren of each area, enabling/disabling each output, etc.
Remote Programming Software, i.e. RPS, includes Bosch A-Link Plus software and the third-
party software of integrated with Bosch SDK.
The IP remote connection function allows to establish a connection from the remote PC to the
alarm control panel through LAN or WAN to perform remote programming and control.
While the connection is established, alarm control panel sends a polling telegram of 25 bytes.
IP Address
RPC IP address is a fixed IP address for remote programming software.
Port Number
RPC port number is the port number of the remote programming software.
DHCP Update / RPC poll Time Interval
DHCP update / RPC poll time is the interval the alarm control panel connects to the RPC
(Remote Programming PC).
The alarm control panel send UDP data packets to the RPC according to the DHCP Update
Time Interval setting (0=disabled 1-15h Interval), when the Panel is reset and when call back is
finished.
RPC get the Subscriber ID, IP address and port from the UDB data packets (IP No. and Port is
parsed from UDP data packet).
RPC with running RPS (Remote Programming Software = A-Link Plus) saves the received UDP
data packet information's into its own RAM, the information is lost after RPS is closed.
When a connection is started and the IP address set in the Customer Information doesn't
match with the IP Address from the Ram, A-Link opens a window to ask if the new IP Address
and Port should be used.
2013.07 | 03 | F.01U.267.112
When the address 0129-0130 is programmed to 1-99, the system will send periodic
automatic test report every hours specified by the address. If 0129-0130 is programmed
to 0, no periodic test reports will be sent.
When 0131-0134 is set to valid time, the system will send automatic test report at the
same time every day. At this moment, the date and time of the system must be correctly
set. If 0131-0134 is set to be invalid time, the daily regular automatic test report will be
disabled.