en | Settings
System is STAY armed +zone intruder alarm (intruder alarm = instant / interior instant / delay /
interior delay / delay exit / interior delay exit / follower / interior follower / 24h (can be
silenced) / Fire (can be silenced) / Technical Alarm (can be silenced))
System is STAY armed +tamper alarm
(no alarm when panel is disarmed)
7 - Internal Siren
The output is triggered when:
System is AWAY armed +zone intruder alarm (intruder alarm = instant / interior instant /
delay / interior delay / delay exit / interior delay exit / follower / interior follower / 24h (can be
silenced) / Fire (can be silenced) / Technical Alarm (can be silenced))
System is AWAY armed +tamper alarm
System is STAY armed +zone intruder alarm (intruder alarm = instant / interior instant / delay /
interior delay / delay exit / interior delay exit / follower / interior follower / 24h (can be
silenced) / Fire (can be silenced) / Technical Alarm (can be silenced))
System is AWAY armed +tamper alarm
System is disarmed +zone tamper alarm
When panel is armed = one pulse activation (1sec) (enabled/disable option can be combined
with disarm)
When panel is disarmed = two pulse activation (1sec) (enabled/disable option can be
combined with arm)
When Programming mode is entered = one pulse activation (1sec) (enabled/disable option)
8 - Internal Siren with tamper
The output is triggered when Internal Siren with tamper.
9 - Entry/Exit Delay Warning
Entry Delay Warning
This output operates during Entry Time.
The output is reset:
1.
2.
3.
Exit Delay Warning
This output operates during Exit Time when the control panel is armed.
The output is reset:
1.
2.
3.
If this duration is programmed as 000, the output will continue till the delay warning duration
is up.
10 - Telephone Line Fault
This output operates when a telephone line fault occurs.
The output is reset:
1.
2.
If this duration is programmed as 000, the output will continue till the telephone line is
restored and fault is reset.
2013.07 | 03 | F.01U.267.112
When the system disarmed
When Entry Time expires
When the output programmed duration is up.
When the system is disarmed
When Exit Time expires
When the output programmed duration is up.
When the Telephone line is restored and fault is reset.
When the output programmed duration is up.