Immediate Load Shedding Example - Cisco Catalyst 3750-X Software Configuration Manual

Hide thumbs Also See for Catalyst 3750-X:
Table of Contents

Advertisement

Understanding StackPower
Graceful load shedding is always enabled and immediate load shedding occurs only when necessary, so
both can occur at the same time.
Load shedding does not occur in redundant mode unless two or more power supplies fail, because the
Note
largest power supply is used as a backup power source.
Notes on load shedding:

Immediate Load Shedding Example

For power stacks in power-sharing mode, if a large power supply in the power stack fails, the stack
immediately starts shutting down powered devices until the power budget matches the input power. This
example has a power stack of four switches (Powerstack1) in power sharing mode and shows which
devices would be shut down in the immediate load shedding process caused by loss of either of two power
supplies.
The output of the show env all command shows that power supplies included in power sharing are a
715 W power supply in switch 1, and one 350 W and one 1100 W power supply in switch 4. Other power
supplies are inactive (disabled or not present).
Switch# show env all
FAN 1 is OK
FAN 2 is OK
FAN PS-1 is OK
FAN PS-2 is OK
TEMPERATURE is OK
Temperature Value: 30 Degree Celsius
Temperature State: GREEN
Yellow Threshold : 49 Degree Celsius
Red Threshold
SW
--
1A
1B
2A
2B
3A
3B
4A
4B
<output truncated>
Catalyst 3750-X and 3560-X Switch Software Configuration Guide
9-4
The method (immediate or graceful) is not user-configurable, but is based on the power budget.
Immediate load shedding also occurs in the order of configured priority, but occurs very quickly to
prevent hardware damage caused by loss of power.
If a switch is shut down because of load shedding, the output of the show stack power privileged
EXEC command still includes the MAC address of the shut down switch as a neighbor switch, even
though the switch is down. This command output shows the StackPower topology, even if there is
not enough power to power up a switch.
: 59 Degree Celsius
PID
Serial#
------------------
----------
NG3K-PWR-715WAC
LIT133705FH
C3KX-PWR-715WAC
DTN1341K018
Not Present
C3KX-PWR-325WAC
LIT13330FNM
C3KX-PWR-325WAC
LIT13330FN3
Not Present
C3KX-PWR-350WAC
DTN1342L00T
NG3K-PWR-1100WAC
LIT13370577
Chapter 9
Status
Sys Pwr
---------------
-------
OK
Good
Disabled
Good
Disabled
Good
Disabled
Good
OK
Good
OK
Good
Configuring Catalyst 3750-X StackPower
PoE Pwr
Watts
-------
-----
Good
715/0
Good
715/0
Good
325/0
Good
325/0
Good
350/0
Good
1100/0