The back of the PDU+ shows (from left to right):
Left: is the management interface with RJ45 LAN and RJ45 serial console
port, RS232 serial port (DB-9) interface, reset button, input voltage status
LED, and switches.
Middle:12x IEC-320-C13 outlets. The outlets on the back are protected by six
branch type circuit breakers 20A. Each pair of C13 outlets is linked to a load
group, six load groups overall.
Right: UTG0247 inlet connector
The front of this PDU+ has no outlets.
IBM Enterprise DPI C19 PDU+
Figure 6-34 shows the back and front of the C19 DPI Enterprise PDU+, part
number 39M2818.
Figure 6-34 IBM Enterprise DPI C19 PDU+ UTG connector, part number: 39M2818
The back of the PDU+ shows (from left to right):
Left: Management interface with RJ45 LAN, RJ45 serial console port, RS232
serial port (DB-9) interface, reset button, input voltage status LED, and
operating DIP switch.
Middle: 6x IEC-320-C19 outlets
Right: UTG0247 inlet connector
The front of the PDU+ has 3x IEC-320-C13 outlets on the right.
The outlets are protected by six branch type circuit breakers 20A. Each of the
C19 outlets on the front represents one load group, to six load groups overall.
Every one of the C13 outlets at the back of the PDU+ is shared with load group 1,
3, or 5 at the C19 outlets.
IBM Ultra Density Enterprise PDU+
Figure 6-35 on page 363 shows the front of the C19 DPI Enterprise PDU+, part
number 71762MX.
362
Planning, Installing, and Managing the IBM System x3950 M2