Mechanical Requirements - Juniper E SERIES BROADBAND SERVICES ROUTERS 11.3.X - ERX HARDWARE GUIDE REV 26-9-2010 Hardware Manual

E series broadband services routers
Table of Contents

Advertisement

ERX 11.3.x Hardware Guide

Mechanical Requirements

122
Figure 52: ERX Routers Installed in a Rack
ERX310 router
ERX7xx model
Plenum
ERX14xx model
Follow these mechanical requirements for your rack:
Select from the following rack options:
Two-post rack—A freestanding enclosed cabinet with two mounting posts in the
front
Telco-type rack—Two adjacent mounting posts that you must secure to the floor or
an overhead structure
Four-post rack—A freestanding open rack, either open or closed
The rack must have at least two mounting posts.
The distance between the mounting holes in the two posts must be 18.31 inches ±.063
inch, as specified in the EIA-310-D.
Do not use an enclosed rack for ERX7xx models or the ERX310 router. It does not provide
adequate ventilation.