Output Hold/Clear Setting - Omron GRT1 - 11-2007 Operation Manual

Slice i/o units
Table of Contents

Advertisement

Functions of Digital I/O Units
4-4-7

Output Hold/Clear Setting

1,2,3...
4. After checking that the setting for the monitor value is reflected in the Edit
Unit Parameters Window, click the General Tab, click the Download But-
ton, and then click the Reset Button.
5. Click the OK Button.
Set the output's hold/clear setting to specify the output status when an error
occurs in the Output Unit. This example shows how to use the DeviceNet
Configurator (version 2.43 or higher) to set the Output Hold/Clear setting.
1. Open the Network Configuration Window and double-click the desired
Slice I/O Terminal's icon or right-click the icon and select Parameters -
Edit to display the Edit Device Parameters Window.
2. Select the desired Slice I/O Unit from the list on the I/O Module Tab Page
and click the Edit Button to display the Edit Unit Parameters Window.
3. Click the OUT Tab.
4. Double-click the desired device's output to display the following window.
Set the status of the Output Unit's outputs for bus errors and communica-
tions errors.
Output status for bus
errors (Fault Action)
Output status for communi-
cations errors (Idle Action)
Sets the status of outputs when an error occurs in
the Slice I/O Terminal's slice bus.
Sets the status of outputs when an error occurs in
host communications (such as DeviceNet).
Section 4-4
59