Omron GRT1 - 11-2007 Operation Manual page 336

Slice i/o units
Table of Contents

Advertisement

Explicit Messages
Explicit
Read
message
/write
Slice Bus
Write/
Sets the Slice Bus error
Error Out-
Read
output value for each
put Setting
output.
0: Hold last state
1: Low limit
2: High limit
3: Zero count
Operation example:
Turnback Cable discon-
nect.
Communi-
Write/
Sets the communica-
cations
Read
tions error output value
Error Out-
for each output.
put Setting
0: Hold last state
1: Low limit
2: High limit
3: Zero count
Operation example:
communications error in
Communications Unit.
Function
Write/
Sets the function.
Setting
Read
Scaling: 0;
Cumulative counter: 1
Scaling
Write/
Default scaling: 0:
Type Set-
Read
User scaling: 1
ting
Scaling
Write/
Sets a conversion value
Point 1 Set-
Read
as the 0% value for user
ting
scaling.
Scaling
Write/
Sets a conversion value
Point 2 Set-
Read
as the 100% value for
ting
user scaling.
Offset
Write/
Sets an offset to com-
Compensa-
Read
pensate for scaling
tion after
error.
Scaling
Cumulated
Read/
Reads the cumulated
Value Read
Reset
analog output value.
Cumulative
Read Reads the cumulative
Counter
count status in the
Flag Read
Cumulative Counter
Flag in the area for
Generic Status Flags.
0: Counter overflow
1: Counter underflow
7: Set value overflow
Function
Service
code
Write:
10 hex
Read:
0E hex
Write:
10 hex
Read:
0E hex
Write:
10 hex
Read:
0E hex
Write:
10 hex
Read:
0E hex
Write:
10 hex
Read:
0E hex
Write:
10 hex
Read:
0E hex
Write:
10 hex
Read:
0E hex
Read:
0E hex
Reset:
35 hex
Read:
0E hex
Command
Class
Instance
Attribute
ID
ID
ID
90 hex 01 to 40
6C hex
*1
hex
*3
82 hex
90 hex 01 to 40
6D hex
*1
hex
*3
83 hex
90 hex 01 to 40
6F hex
*1
hex
*3
85 hex
90 hex 01 to 40
*2
70 hex
*1
hex
*3
86 hex
90 hex 01 to 40
*2
71 hex
*1
hex
*3
87 hex
90 hex 01 to 40
*2
72 hex
*1
hex
*3
88 hex
90 hex 01 to 40
*2
73 hex
*1
hex
*3
89 hex
90 hex 01 to 40
*2
77 hex
*1
hex
8D hex
90 hex 01 to 40
*2
78 hex
*1
hex
8E hex
Appendix A
Response
Data Size
*2
1 byte
1 byte
1 byte
1 byte
*2
*2
1 byte
1 byte
1 byte
2 bytes
2 bytes
(−28000 to
(−28000 to
28000)
28000)
2 bytes
2 bytes
(−28000 to
(−28000 to
28000)
28000)
2 bytes
2 bytes
(−28000 to
(−28000 to
28000)
28000)
4 bytes
(−214748364.8
*3
to
214748364.8)