Omron GRT1 - 11-2007 Operation Manual page 347

Slice i/o units
Table of Contents

Advertisement

Explicit Messages
Explicit
Read/
message
write
Action on
Read
Reads the action
Rising Edge
performed on the
of Digital
rising edge of the
Input
digital input.
Write
Writes the action
performed on the
rising edge of the
digital input.
Action on
Read
Reads the action
Falling Edge
performed on the
of Digital
falling edge of the
Input
digital input.
Write
Writes the action
performed on the
falling edge of the
digital input.
Action on
Read
Reads the action
Bus Error
performed when
a bus error
occurs.
The same setting
applies to all out-
puts.
Write
Writes the action
performed when
a bus error
occurs.
The same setting
applies to all out-
puts.
Configura-
Read
Reads the
tion Tag
present value of
the configuration
tag.
Write
Writes the value
of the configura-
tion tag.
Range 0
Write
Writes the upper
and lower limits of
range 0.
Save
Write
Writes the range
Ranges and
settings and pre-
Preset Val-
set value to non-
ues
volatile memory.
326
Function
Service
Class
code
0E hex
8E hex 01 to 40
10 hex
8E hex 01 to 40
0E hex
8E hex 01 to 40
10 hex
8E hex 01 to 40
0E hex
8E hex 01 to 40
10 hex
8E hex 01 to 40
0E hex
8E hex 01 to 40
10 hex
8E hex 01 to 40
33 hex
8E hex 01 to 40
*3
10 hex
8E hex 01 to 40
Command
Instance
Attribute
ID
ID
ID
91 hex
*1
hex
91 hex
*1
hex
92 hex
*1
hex
92 hex
*1
hex
93 hex
*1
hex
93 hex
*1
hex
94 hex
*1
hex
94 hex
*1
hex
95 hex
*1
hex
97 hex
*1
hex
Appendix A
Response
Data size
1 byte
---
00 hex: No action
01 hex: Capture
02 hex: Reset
03 hex: Preset
1 byte
---
00 hex: No action
01 hex: Capture
02 hex: Reset
03 hex: Preset
1 byte
---
00 hex: No action
01 hex: Capture
02 hex: Reset
03 hex: Preset
1 byte
---
00 hex: No action
01 hex: Capture
02 hex: Reset
03 hex: Preset
1 byte
---
00 hex: Outputs
are cleared on bus
error.
01 hex: Output
functionality is
maintained on bus
error.
1 byte
---
00 hex: Outputs
are cleared on
bus error.
01 hex: Output
functionality is
maintained on
bus error.
1 byte
---
Range of values:
00 to FF hex
(0 to 255 decimal)
1 byte
---
Range of values:
00 to FF hex
(0 to 255 decimal)
2 × 4 bytes
---
Range of values:
8000 0000 to
7FFF FFFF hex
(-2,147,483,648
to 2,147,483,647
*4
decimal)
1 byte
---
Value: 00 hex

Advertisement

Table of Contents
loading

This manual is also suitable for:

Smartslice - 11-2007Smartslice grt1 series

Table of Contents