Editing Device Parameters
3-1-8

Safety Output Logic Parameter Groups (Safety Output Logic)

Parameter name
S
Output Condition
S
Welding Check (EDM)
Feedback
S
Additional Output Data
S
Off On Delay
S
On Off Delay
Note
36
Safety output parameter groups can only be set for the DST1-XD0808SL-1.
Set these parameters using the Safety Logic Wizard.
Value
Output from network
Uses a safety output terminal as a network output.
The value (safety output) received from the net-
work is directly output.
Logic operations for
Uses the output as a safety output terminal logic
safety input logic opera-
output. The logic operation result is output. Set
tion results and remote
logic operations for safety input logic operation
I/O signals (output from
results and remote I/O (received from the Master).
internal logic)
Additional output
Uses a safety output terminal as an additional out-
put terminal. Select the data to be output as the
additional output data.
Not Used
EDM feedback is not used.
IN4
EDM feedback is used. Select the terminals for
connecting feedback signals from external devices.
IN5
IN6
IN7
Not Used
This setting is enabled when the safety output con-
dition is set to additional output.
OUT0
Outputs the same value as OUT0.
OUT0 (NOT)
Outputs the inverse value of OUT0.
OUT2
Outputs the same value as OUT2.
OUT2 (NOT)
Outputs the inverse value of OUT2.
OUT4
Outputs the same value as OUT4.
OUT4 (NOT)
Outputs the inverse value of OUT4.
OUT6
Outputs the same value as OUT6.
OUT6 (NOT)
Outputs the inverse value of OUT6.
Reset Required Indica-
Outputs a 1-Hz pulsing signal to trigger a reset
tion
input.
RUN Status Flag
Outputs the operating mode.
0: Not RUN mode
1: RUN mode
Normal Status Flag
Outputs the status.
0: Error (See note 1.)
1: Normal
0 to 300,000 ms (Unit:
Sets the ON delay time.
100 ms)
0 to 300,000 ms (Unit:
Sets the OFF delay time.
100 ms)
(1) Turns OFF (0) when one of the errors shown in 7-3 Error History occurs.
(2) Safety output parameter groups can be set only for DST1-XD0808SL-1
safety outputs OUT0 to OUT7. For details on DST1-XD0808SL-1 logic
functions, refer to 1-5 Logic Functions.
Description
Section 3-1
Default
Output
from net-
work
Not Used
Not Used
0 ms
0 ms