Omron GRT1 - 11-2007 Operation Manual page 140

Slice i/o units
Table of Contents

Advertisement

Analog Input Units
Setting Procedure (Example: DeviceNet Configurator)
1,2,3...
turned ON may be the data from when the Hold Flag was OFF. To collect
peak/bottom hold data using the Hold Flag at the Master, configure a ladder
program that considers the transmission delay when the Hold Flag is turned
ON, then enables the peak/bottom hold values after a fixed time interval.
1. In the Network Configuration Window for the Slice I/O Terminal, double-
click the icon of the Slice I/O Terminal that is to be set. Alternatively, right-
click the icon and select Parameters - Edit. The Edit Device Parameters
Window will be displayed.
2. Click the I/O Module Tab.
3. Click the Edit Button on the I/O Module Tab Page. The Edit Unit Parame-
ters Window will be displayed.
4. Select the tab page for the input where peak/bottom hold is to be set, and
select the Peak/Bottom Hold Check Box in the Function Choice Area.
Section 5-4
119