Explicit Messages
Command Details
• [CMND S
D
S: D01000
D (first response word): D02000
C: D00000
Contents of S
Address
D01000
28 01
D01001
0B 0E
D01002
00 8E
D01003
00 01
8C **
D01004
Contents of C
Address
D00000
00 09
D00001
00 0C
D00002
00 00
D00003
05 FE
D00004
00 00
D00005
00 3C
Response
Contents of D
Address
D02000
28 01
D02001
00 00
D02002
00 02
D02003
0B 8E
D02004 to D02005
00 00
C]
Contents (hex)
Command code
DeviceNet Communications Unit's node address: 11
Service code: 0E hex
Class ID: 008E hex
Instance ID: 0001 hex
Attribute ID: 8C ** hex (Set any value for the blank digits.)
Contents (hex)
Number of bytes of command data
Number of bytes of response data
Destination DeviceNet Unit's network address: 0
Destination DeviceNet Unit's node address: 5
Destination DeviceNet Unit's unit address: FE hex (or 10 hex)
Response required
Communications port number: 0
Number of retries: 0
Response monitoring time: 6 s
Contents (hex)
Response source node address: 11 (0B hex)
Normal completion: 8E hex
Operation time monitor peak value