Data Memory (DM) Allocation
Note
Simple Communications Unit Control (Offset: +0)
Bits
Setting
0 to 3
RUN/Stop
0
(Digit 16
)
4 to 7
Communications
timeout
1
(Digit 16
)
8 to 15
Number of con-
nected components
2
(Digits 16
3
and 16
)
238
Offset
+5
Communications control for Units 16 to 23
+6
Communications control for Units 24 to 31
+7
Unit 0 communications type
+8
Starting address of Unit 0 read data area
(Starting address of Unit 0 read variable type area*
+9
Starting address of Unit 0 write data area
(Starting address of Unit 0 write variable type area*
+10
Unit 1 communications type
+11
Starting address of Unit 1 read data area
(Starting address of Unit 1 read variable type area*
+12
Starting address of Unit 1 write data area
(Starting address of Unit 1 write variable type area*
:
:
+100
Unit 31 communications type
+101
Starting address of Unit 31 read data area
(Starting address of Unit 31 read variable type area*
+102
Starting address of Unit 31 write data area
(Starting address of Unit 31 write variable type area*
1. These words are used to notify the CPU Unit of the Simple Communica-
tions Unit's status.
2. The functions in parentheses are for CompoWay/F communications.
Range
1: RUN
If this digit is set to 1 after the power is turned ON, the Simple Communica-
0: Stop
tions Unit will start communications with components and the CPU Unit. (If
a fatal error has occurred, the Unit will not start communications with com-
ponents even if this digit is set to 1.)
The Simple Communications Unit will not communicate with components if
this digit is set to 0.
0 to 9
Sets the response monitoring time for access from the Simple Communica-
(BCD)
tions to connected components. The timeout time is set in multiples of
500 ms ((Set value + 1) × 500 ms). This setting is usually set to 0, which
sets a response monitoring time of 500 ms.
00 to 32
Specifies the number of components connected to the Simple Communica-
(BCD)
tions Unit. The Simple Communications Unit will not communicate with
components if the number of connected components is set to 0.
Function
2
)
2
)
2
)
2
)
:
:
2
)
2
)
Function
Section 7-4