Troubleshooting Flowcharts - Omron CPM2C Operation Manual

Sysmac series programmable controller
Hide thumbs Also See for CPM2C:
Table of Contents

Advertisement

Troubleshooting Flowcharts

5-5

Troubleshooting Flowcharts

Main Check
200
Use the following flowcharts to troubleshoot errors that occur during opera-
tion.
Error
PWR indicator lit?
Yes
RUN indicator lit?
Yes
ERR/ALM indicator
flashing?
Not lit
Is I/O sequence
normal?
Yes
Operating
environment normal?
Yes
Replace the CPU
Unit.
No
Check power supply.
No
Operation stopped. Check for fatal errors.
(See page 202.)
Flashing
Check for non-fatal errors.
No
(See page 204.)
Check I/O.
No
Check operating environment.
Section 5-5
(See page 201.)
(See page 203.)
(See page 206.)