 Safety Wiring
In PLC control system, many devices are controlled at the same time and actions of any
device could influence each other, i.e. breakdown of any device may cause the
breakdown of the entire auto-control system and danger. Therefore, we suggest you
wire a protection circuit at the power supply input terminal. See the figure below.
AC power supply:100 ~ 240VAC, 50/60Hz
1
Emergency stop: This button cuts off the system power supply when accidental
3
emergency takes place.
Power indicator
4
Power supply circuit protection fuse (2A)
6
DC power supply output: 24VDC, 500mA
8
DC power supply: 24VDC
10
Digital I/O module (AC supply)
12
DC power supply: 20.4VDC~28.8VDC
14
 I/O Point Wiring
There are 2 types of DC inputs, SINK and SOURCE. (See the example below. For
detailed point configuration, please refer to the specification of each model.)
 DC Signal IN – SINK mode
Input point loop equivalent circuit
+24V
24G
S/S
X0
X1
[ Figure 5 ]
 Relay (R) output circuit wiring
Breaker
2
AC power supply load
5
DVP-PLC (main processing unit)
7
Grounding resistance: < 100Ω
9
Digital I/O module (DC supply)
11
Analog I/O module (DC supply)
13
 DC Signal IN – SOURCE mode
Input point loop equivalent circuit
+24V
24G
S/S
X0
X1
[ Figure 6 ]
- 5 -
[ Figure 7 ]