Siemens 8DJH Series Installation And Operating Instructions Manual page 45

Medium-voltage switchgear
Table of Contents

Advertisement

Arcing time
Break time
Close-open contact time
Motor operating
mechanism
Closing solenoid (Y9)
500-8067.9 * INSTALLATION AND OPERATING INSTRUCTIONS 8DJH * Revision 03
The interval of time from the first initiation of an arc and the instant of final arc extinction
in all poles.
The interval of time between the initiation (command) of the opening operation and
the instant of final arc extinction in the last-pole-to-clear (=opening time and arcing time).
The interval of time - in a make-break operating cycle - between the instant when
the contacts touch in the first pole in the closing process, and the instant when
the contacts separate in all poles in the subsequent opening process.
For DC operation, the maximum power consumption is approx. 350 W.
For AC operation, the maximum power consumption is approx. 400 V A
The rated current of the motor protection equipment is shown in the following table:
Rated supply voltage
V
DC 24
DC 48
DC 60
DC/AC 110
50/60 Hz
DC 220/AC 230
50/60 Hz
*) M.c.b. with C-characteristic
The supply voltage may deviate from the rated supply voltage specified in
the table by -15% to +10%.
The breaking capacity of the auxiliary switch 3SV92 is shown on the following table:
Breaking capacity
Operating voltage [V]
AC 40 to 60 Hz
up to 230
DC
24
48
60
110
220
The closing solenoid closes the circuit-breaker. After completion of a closing operation,
the closing solenoid is de-energized internally. It is available for AC or DC voltage.
Power consumption: 140 W or 140 VA.
Recommended rated current for
the protection equipment*
Type 1.1
A
8
6
4
2
1.6
Normal current [A]
10
Resistive load
Inductive load
10
10
10
9
9
7
5
4
2.5
2
Description
45