Installation
Switchgear storage in
closed rooms
62
11.3

Intermediate storage

DANGER!
Risk of injury and damage to the stored goods if the storage space is overloaded.
Observe the load-bearing capacity of the floor.
Do not stack the transport units.
Do not overload lighter components by stacking.
ATTENTION!
Fire risk. The transport unit is packed in flammable materials.
No smoking.
Keep fire extinguishers in a weatherproof place.
Mark the location of the fire extinguisher.
ATTENTION!
Supplied desiccant bags lose their effectiveness if they are not stored in
the undamaged original packings.
Do not damage or remove packing of desiccant bags.
Do not unpack desiccant bags before use.
If the comprehensive accessories, the delivered switchgear or parts thereof have to be
stored before installation, a suitable storage room or place has to be selected and
prepared.
Intermediate storage of the transport units:
• In original packing as far as possible
• Switchgear with secondary system: Observe the permissible storage temperature
from -25° C to +70° C in accordance with the installed secondary devices.
• Switchgear without secondary system: Observe the permissible storage temperature
from -40° C to +70° C.
• In a weatherproof place
• Protected against damage
• If packed in seaworthy crates, the switchgear can be stored for a maximum of
6 months (desiccant bags)
• Store transport units in such a way that they can be taken out later in the correct order
for installation.
As a rule, the switchgear should be stored in a closed room. The storage room must
have the following characteristics:
• Floor with adequate load-bearing capacity (weights as per delivery note)
• Even floor to enable stable storage
• Well-ventilated and free of dust as far as possible
• Dry and protected against humidity and vermin (e.g. insects, mice, rats)
• Check humidity in the packings every 4 weeks (condensation)
• Do not unpack small parts to avoid corrosion and loss.