Description
Mechanism operation
Motor operating
mechanism (optional)
16
Sequence
Operation
Switch position
Position indicator
"Spring charged" indicator
Closing spring
Opening spring
Equipment
Operating lever for charging the springs of the switch-disconnector and the make-proof
earthing switch. Coding of the operating levers is optionally possible.
Operation
• Local operation by momentary-contact rotary control switch (option)
• Remote operation (standard) applied to terminal
Operating voltages for motor operating mechanisms and tripping coils
• 24, 48, 60, 110, 220 V DC
• 110 and 230 V AC 50/60 Hz
Fig. 7:
Motor unit with auxiliary switch block
Revision 03 * INSTALLATION AND OPERATING INSTRUCTIONS 8DJH * 500-8067.9
1
2
Charging the
springs
OPEN
OPEN
not charged
charged
not charged
charged
3
4
CLOSED
OPEN
not charged
not charged
charged
not charged