Installation
Mount cable plug type Rayschem RICS5xxx with surge arrester RAD according to
the manufacturer's instructions (see order documents).
Fasten adapter feet with hexagonal nuts M12 and strain washers to the surge
arrester plate.
s
Fig. 59: Push the surge arrester plate
between the hexagonal nuts M12 of the adapter feet,
a
d
and tighten it. Use hexagonal nuts M12
with strain washers
.
Fasten upper cross member with two bolt-and-washer assemblies M8 x 20.
a
Fig. 60: Mounting bolt-and-washer assemblies
on
the upper cross member.
Fasten the surge arrester plate with two bolt-and-washer assemblies M8 x 20 and
washers to the upper cross member.
500-8067.9 * INSTALLATION AND OPERATING INSTRUCTIONS 8DJH * Revision 03