Siemens 8DJH Series Installation And Operating Instructions Manual page 49

Medium-voltage switchgear
Table of Contents

Advertisement

Switchgear weights
500-8067.9 * INSTALLATION AND OPERATING INSTRUCTIONS 8DJH * Revision 03
The weight of the switchgear unit results from the sum of the weights per functional
unit. Depending on the design and the degree to which it is equipped (e.g. current
transformers, motor operating mechanism, low-voltage compartment), different values
will result. The table shows mean values.
Panel type
Width [mm]
R
310
R(500)
500
K
310
K(E)
430
T
430
L
430
L (type 1.1) without 4MT3 500
L (type 2)
500
Panel block
Width [mm]
KT,TK
740
K(E)T
860
KL*,LK
740
K(E)L*
860
RK, KR
620
RT, TR
740
RL*, LR
740
TT
860
RR
620
LL*
860
RRT
1050
RRL*
1050
RTR
1050
RLR
1050
RRR
930
TTT
1290
LLL*
1290
RRRT
1360
RRRL*
1360
RRRR
1240
TRRT
1480
LRRL
1480
TTTT
1720
LLLL*
1720
* Applies to design with circuit-breaker type 2
Gross weight for a switchgear height of
1200 mm
1400 mm
approx. [kg]
approx. [kg]
100
110
140
150
100
110
130
140
135
145
130
140
210
220
160
170
Gross weight for a switchgear height (without low-voltage
compartment) of
1200 mm
1400 mm
approx. [kg]
approx. [kg]
230
250
240
260
230
250
250
270
200
220
230
250
230
250
270
290
200
220
260
280
330
360
320
350
330
360
320
350
300
330
410
440
400
430
430
470
430
470
400
440
470
510
460
500
540
580
520
560
Description
1700 mm
approx. [kg]
120
170
120
160
160
155
240
190
1700 mm
approx. [kg]
280
290
280
300
240
280
280
320
240
310
400
390
400
390
360
490
480
520
520
480
560
550
640
620
49

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents