Siemens 8DJH Series Installation And Operating Instructions Manual page 13

Medium-voltage switchgear
Table of Contents

Advertisement

Mode of operation
Closing operation
Opening operation
Earthing operation
Common features
Features of spring-
operated/stored-energy
mechanism
Assignment of operating mechanism type of three-position switch to panel types
Panel type
R, L
Function
Switch-disconnector (R)
Disconnector (L)
Type of operating
Spring-operated
mechanism
Operation
Manual
Motor (option)
Design
500-8067.9 * INSTALLATION AND OPERATING INSTRUCTIONS 8DJH * Revision 03
The operating shaft forms one unit together with the three contact blades.
Due to the arrangement of the fixed contacts (earth - busbar), it is not necessary to
interlock the CLOSE and EARTHING functions.
During the closing operation, the operating shaft with the moving contact blades
changes from the "OPEN" to the "CLOSED" position.
The force of the spring-operated mechanism ensures a high closing speed and
a reliable connection of the main circuit.
During the opening operation, the arc is caused to rotate by the arc-suppression system,
thus preventing the development of a fixed root. This very effective arc extinction
provides short arcing times. The isolating distance in gas established after opening
satisfies the conditions for isolating distances according to IEC/EN 60 265-1 /
VDE 0671-102 and IEC/EN 62 271-1 / VDE 0671-1.
The "EARTHING" operation is implemented by the turning movement of the operating
lever (rotation, if required) from the "OPEN" to the "EARTHED" position.
Operating mechanisms for the three-position switch
• Mechanical endurance of more than 1000 operating cycles
• Manual operation with the help of a slip-on operating lever
• Option: Motor operation of the disconnecting function
• Control board with accordingly cut-out switching gate prevents the three-position
switch-disconnector from being switched directly from the CLOSED via the OPEN to
the EARTHED position.
• Two separate actuating openings are provided for unambiguous selection of either
the load-break function or make-proof earthing.
• Operation via rotary movement, operating direction according to IEC/EN 60 447
(VDN/VDEW recommendation).
The switching movements are performed independently of the operating speed.
During the charging process, the closing and opening springs are charged. This ensures
that the switch-disconnector/fuse combination can switch off all types of faults reliably
even during closing.
Closing and opening is done via pushbuttons after removing the operating lever, and is
therefore identical with the operation of circuit-breaker operating mechanisms.
An energy store is available for tripping by means of an operating HV HRC fuse or
via a shunt release (f-release).
After the HV HRC fuse has tripped, a red crossbar appears on the "fuse tripped" indicator.
Manual operation for the EARTHING function with the help of a slip-on operating lever.
Earthing switch
Spring-operated
Manual
The three-position switch-disconnector is operated through a gas-tight welded bushing
at the front of the switchgear vessel.
T
Switch-disconnector
Stored-energy
Manual
Motor (option)
Description
Earthing switch
Spring-operated
Manual
13