Operation
Inserting
the HV HRC fuse slides
122
Push the cover of the HV HRC fuse-link (on the opposite side of the housing cover)
aside, and pull the HV HRC fuse out of the fuse slide.
Fit new HV HRC fuse-link into the contact springs observing the striker position.
The arrow on the HV HRC fuse points to the housing cover.
Verify correct seating of the covers and the fuse.
ATTENTION!
Incorrectly selected or mounted fuse-links and extension tubes can damage
the fuse box or the switchgear.
7 .2 kV fuse-links with dimension 192 mm and 24 kV fuse-links with
dimension 292 mm are not permissible.
Revision 03 * INSTALLATION AND OPERATING INSTRUCTIONS 8DJH * 500-8067.9