500-8067.9 * INSTALLATION AND OPERATING INSTRUCTIONS 8DJH * Revision 03
If necessary, detach the cross members
Pre-adjust the cable bracket
If available, mount cable-type current transformers (see Page 93, "Cable connection
with cable-type current transformers".
Fit the plugs on the conductor ends according to the manufacturer's instructions.
Carefully coat the push-on surfaces (high-quality joints) in the plug sets and the
bushing cone with mounting paste (scope of supply of the plug set).
a
Push the plug sets
manufacturer's instructions. Observe the phase sequence!
Mount the upper part of the cable clamps
Connect the cable shield and the earthing of the plug housing at the front cross
j
member
.
Double cables and surge arresters can be connected to ring-main feeders using
adequate plug-in cable systems.
Please observe the following:
• Depending on their type, double cable connections require a deep cable compartment
cover and larger floor openings.
• Depending on their type, surge arresters also require a deep cable compartment cover.
For details, please refer to the order documents.
j
to swing in the cables.
g
and the lower part of the cable clamps
d
to
onto the bushing and fix them according to the
h
, align the cable bracket and bolt it tight.
Installation
h
.
85