500-8067.9 * INSTALLATION AND OPERATING INSTRUCTIONS 8DJH * Revision 03
17.4

Closing the three-position disconnector in the circuit-breaker panel type 2

ATTENTION!
Please do absolutely observe the following:
The max. service life of the circuit-breaker panel depends on the permissible
number of switching operations of the switching device used (see Page 44,
"Vacuum circuit-breaker " and see Page 43, "Three-position disconnector ").
Push the control gate of the disconnector upwards. The actuating opening for
the disconnector is free. Only possible with the circuit-breaker in OPEN position.
Insert the operating lever and turn 70° clockwise. The position indicator of
the disconnector in the mimic diagram is in CLOSED position.
Remove the operating lever.
The control gate of the disconnector moves to the center position automatically.
The actuating opening is closed.
The disconnector is closed.