Siemens 8DJH Series Installation And Operating Instructions Manual page 30

Medium-voltage switchgear
Table of Contents

Advertisement

Description
Features
Cable sealing ends
Option
Plug systems
30
Cable connections with bolted contact for transformer feeders
Fig. 22: Cable connection for transformer feeder: Interface type C (630 A):
E.g. Euromold K400 TB (black), nkt AB 24-630 and ASA 24-5 (gray)
• As plug-in contacts according to EN 50 181/DIN EN 50 181 interface type A for cable
elbow plugs or straight cable plugs
• For bushings according to EN 50 181/DIN EN 50 181 interface type C with bolted
contact M16
The transformer cables are connected with cable plugs.
• Mounted cable clamps on cable bracket
• Bolted contact (M16)
Selection table for plug systems
Manufacturer
Euromold
nkt cables
Südkabel (ABB)
Prysmian Kabel (Pirelli)
Tyco Electronics Raychem
Cooper
Further plug types on request
Revision 03 * INSTALLATION AND OPERATING INSTRUCTIONS 8DJH * 500-8067.9
Plug type for ring-main feeders
(K) 400 TB (S)
(K) 400 LB
- - -
CB 24-630
AB 24-630
-
SEHDT 13 (23)
SEHDT 13.1 (23.1)
FMCTs(m)-400
RICS 51 ...
DT 400 P
Plug type for transformer feeders
(K) 158 LR
(K) 151 SR
AGW (L) 10 (20); AGG (L) 10 (20)
CE 24-250
EASW 10/250
EASW 20/250
SEHDG 11.1 (21.1)
SEW 12 (24)
FMCE(m)-250
RSES; RSSS
DE 250; DS 250