Operator control (hardware)
3.1
Control Elements
3.1.1
Mode selector
Certain operating modes can be selected using the mode selector.
Mode selector positions
The mode selector positions are explained in the order in which they are arranged on the
SIMOTION C.
Table 3-1
Operating
mode
RUN
STOPU
SIMOTION C
Operating Instructions, 11/2022, A5E33441428B
Modes and switch settings
Explanations
SIMOTION C executes the user program (UP) and the associated system functions:
•
Reading process image of inputs
•
Execution of the user programs assigned to the execution system
•
Writing process image of outputs
The technology packages are active in this state. They can execute commands from the
user program.
Note:
With the C230-2, the key cannot be removed in this position.
SIMOTION C does not execute a user program.
•
The technology packages are active. Test and commissioning functions can be exe‐
cuted. The user program is not active.
•
The I/O modules (SMs) are in a safe state.
With the C230-2, the key can be removed in this position so that no unauthorized person
can change the operating modes.
Note:
The toggle switch of the C240 / C240 PN does not have the "STOPU" switch setting.
You can switch to "STOPU" mode only via the SIMOTION SCOUT engineering system.
In SIMOTION SCOUT, you can switch from the hardware settings "STOP" and "RUN" to
"STOPU" mode.
3
39