Interfaces
4.5 Onboard drive interface (C230-2, C240)
Use as standard outputs (analog/digital output) for C240
The setpoint signals (connector X2, SETP1 to 4) can also be used on the C240 as four analog
outputs. The analog output (X2) has a filter that can be switched off.
The default setting is "with filter (C230-2-compatible)". This setting is active regardless of
whether the four outputs are used (actuating signal for axis of analog output). Output values are
interpolated linearly via the servo cycle clock.
Procedure:
1. Select the C240 in the rack.
2. Select the menu command Edit > Object Properties to open the Properties C240 - (R0/S2)
dialog.
3. You can set the filter time in the Onboard I/O tab.
The controller enable contacts (connector X2, CTREN1 to 4) can also be used on the C240 as four
digital outputs. These digital outputs are isolated relay contacts (NO).
Figure 4-7
See also
Overview (Page 66)