Siemens SIMOTION C 230-2 Operating Instructions Manual page 127

Hide thumbs Also See for SIMOTION C 230-2:
Table of Contents

Advertisement

The following bus connectors can be used with the C240 PN:
• SIMATIC NET, Ind. Ethernet FC RJ45 plug 145
Article No.: 6GK1901-1BB30-0AA0 (1 item)
Article No.: 6GK1901-1BB30-0AB0 (10 items)
You can obtain additional information about the different cable systems for PROFINET and
Ethernet from your SIEMENS contact.
Loading the PROFINET configuration via PROFIBUS DP (loading of the IP address)
For configuration using PROFINET, the SIMOTION C must be provided with an IP address, the
subnet mask and the router address.
To configure and transfer PROFINET addresses to the C240 PN, proceed as follows:
1. Open your project.
2. Open HW Config. Double-click the X11 "PNxIO" slot of the C240 PN module to open the
"Properties - PNxIO" dialog box.
3. Click the "Properties" button of the Ethernet interface. The "Properties - PNxIO Ethernet
Interface" dialog box is displayed.
4. In this dialog, click "New". The "New Industrial Ethernet" subnet dialog is displayed. In this
dialog box, you can change the name of the new subnet or confirm the factory setting with
"OK".
5. The newly created Ethernet subnet is now shown under Subnet in the "Properties - Ethernet
Interface" dialog box and must be selected.
6. In this dialog box, enter the required addresses for IP address and subnet dialog box. Under
Router, choose whether a router is to be used. If using a router, enter the router address.
7. Confirm this dialog box with "OK".
8. Close the "Properties - PNxIO" dialog box with "OK".
9. Save and compile the modified hardware configuration.
10.Load the new hardware configuration to the C240 PN via PROFIBUS DP.
SIMOTION C
Operating Instructions, 11/2022, A5E33441428B
Connecting
6.2 Networking
127