Clearances - Siemens SIMOTION C 230-2 Operating Instructions Manual

Hide thumbs Also See for SIMOTION C 230-2:
Table of Contents

Advertisement

Configuring and installing
5.2 Configuring an installation using SIMOTION C modules
Permissible ambient temperature
• Horizontal installation: 0 °C to 55 °C
• Vertical installation: 0 °C to 40 °C
Figure 5-1
5.2.2

Clearances

Rules
If you comply with the minimum clearances, you will:
• Ensure heat is dissipated from the modules
• Provide space to fit and remove modules
• Provide space to lay wiring
• Increase the mounting height of the rack to 205 mm!
To guarantee the functionality, clearances of 40 mm must be maintained.
Note
If you use a shield connecting element, the dimensions stated are measured from the lower
edge of the shield connecting element.
80
Horizontal and vertical configuration
Operating Instructions, 11/2022, A5E33441428B
SIMOTION C