Configuring and installing
5.2 Configuring an installation using SIMOTION C modules
Mounting rail lengths
Depending on the configuration you have chosen, you can use the following mounting rails:
Table 5-2
Mounting rail
160 mm
482.6 mm
530 mm
830 mm
2,000 mm
5.2.4

Layout of modules on a rack

Rules
The following rules apply with respect to the layout of the modules on a rack:
• Up to eight modules can be inserted to the right of the SIMOTION C.
• The number of plug-in modules is also limited by their power consumption from the
backplane bus (see Technical data table for the individual modules in the S7-300 Automation
Systems, M7-300 Module Data Manual).
The total power consumption from the backplane bus of all modules that are mounted on a
rack must not exceed 1.2 A.
This figure shows the order of the modules in an installation with eight I/O modules.
Figure 5-3
Installation of FM STEPDRIVE
The FM STEPDRIVE modules can be installed, in addition to the eight SMs. They have no
connection to the backplane bus and must therefore only be taken into consideration with
regard to the module width. In order to prevent the backplane bus from being interrupted, the
FM STEPDRIVE modules must always be configured as the last modules on the module rack.
82
Mounting rails
Usable length for modules
120 mm
450 mm
480 mm
780 mm
Cut to required length
Layout of modules on a rack
Comments
Mounting holes are provided
Mounting holes are provided
Mounting holes are provided
Mounting holes are provided
Mounting holes must be drilled