Honeywell NOTIFIER FireWarden-100-2 Instruction Manual page 83

Fire alarm control panel
Table of Contents

Advertisement

Master Programming Level
TIMER
1=AC LOSS DELAY
Timer Screen #2
SYSTEM SETUP
1=TIMERS
2=NAC
3=RELAYS
System Setup Screen #2
FireWarden 100-2/E — P/N 52778:A 11/04/2005
AC Loss Delay
The reporting of a loss of AC power to a central station can be delayed by programming the length
of the desired delay. Press 1 while viewing Timer Screen #2 to display the following:
AC LOSS DELAY
1=NO DELAY
2=ENTER DELAY
Pressing 1 while viewing AC Loss Delay Screen #1 will program the FACP to transmit an AC Loss
report immediately to the central station.
Pressing 2 while viewing AC Loss Delay Screen #1 will display the following:
RANGE 00-23
A flashing cursor will appear in the lower left corner of the display. Type the two digit AC loss
reporting delay in hours (00 to 23 hour delay). When the second digit is entered, the display will
return to AC Loss Delay Screen #1.
Important: For Central Station applications, AC Loss Reporting Delay must be set to a delay value
ranging from 06 to 12 hours. For Remote Station applications, AC Loss Reporting Delay must be
set to a delay value ranging from 15 to 23 hours.
NOTE: AC Loss Delay also applies to any programmable output relay programmed for "AC
Loss".
NAC (Notification Appliance Circuit)
The options for the NACs on the control panel main circuit board can be configure by pressing 2
while viewing System Setup Screen #2. The following screens will be displayed:
1=NAC 1
2=NAC 2
The Notification Appliance Circuits can be configured independently by pressing 1 for NAC 1, 2
for NAC 2, 3 for NAC 3 or 4 for NAC 4.
Note that 3=NAC 3 and 4=NAC 4 will be displayed, and can be programmed, regardless of how
the NACKEY card is installed. Their programming, however, will have no effect if the NACKEY
card is installed for Class A operation.
AC Loss Delay Screen #1
AC LOSS DELAY
AC Loss Delay Screen #2
NACS
3=NAC 3
4=NAC 4
NAC Selection Screen
Programming
83

Advertisement

Table of Contents
loading

This manual is also suitable for:

Notifier firewarden-100-2e

Table of Contents