Honeywell NOTIFIER FireWarden-100-2 Instruction Manual page 153

Fire alarm control panel
Table of Contents

Advertisement

Transmittal Priorities
The table below shows UL listed receivers which are compatible with the NFW2-100.
Format #
(Addresses 16 & 42)
0
4+1 Ademco Express
1
4+2 Ademco Express
2
3+1/Standard/1800/2300
3
3+1/Expanded/1800/2300
4
3+1/Standard/1900/1400
5
3+1/Expanded/1900/1400
6
4+1/Standard/1800/2300
7
4+1/Expanded/1800/2300
8
4+1/Standard/1900/1400
9
4+1/Expanded/1900/1400
A
4+2/Standard/1800/2300
B
4+2/Expanded/1800/2300
C
4+2/Standard/1900/1400
D
4+2/Expanded/1900/1400
E
Ademco Contact ID
F
Not Used
1.
With 685-8 Line Card with Rev. 4.4d software
2.
With 9002 Line Card Rev. 9035 software or 9032 Line Card with 9326A software
3.
Rev. 4.0 software
4.
FBI CP220FB Rec-11 Line Card with Rev. 2.6 software and a memory card with Rev. 3.8
software
5.
Model 6500 with Rev. 600 software
6.
Mode 6000 with Rev. 204 software
7.
With Rev. B control card at Rev. 1.4 software and Rev. C line card at Rev. 1.5 software
8.
Model 2 only
9.
Version 1.62 software
IMPORTANT! It is the installer's responsibility to ensure that the Digital Alarm
Communicator/Transmitter is compatible with the Central Station Receiver, utilized by the
monitoring service, prior to installation. The Compatibility Table provides a list of compatible
receivers and associated software versions for the receivers. Changes in the hardware and/or
software by the receiver manufacturers may affect the receiver compatibility with the FACP DACT.
After completing the installation, communication between the DACT and Central Station Receiver
must be tested and verified.
FireWarden 100-2/E — P/N 52778:A 11/04/2005
Table 5.3 Compatible UL Listed Receivers
Central Station Communications
(8)
(4)
(4)
(4)
(4)
(4)
(4)
(4)
(4)
(4)
(4)
(4)
(4)
153