Programming
The factory default setting for Pre-signal delay is 000 for no delay. To select a Pre-signal delay of
001 to 180 seconds for all devices programmed for Pre-signal, press 2 while viewing Timer Screen
#1. The following screen will be displayed:
A flashing cursor is positioned in the lower left corner of the display. Enter a delay time consisting
of three digits, such as 009 for nine seconds. Upon entering the third digit, the time delay will be
stored in the control panel memory and the display will return to the Delay Screen which will
indicate the new delay time.
Note that the FACP can be programmed for either PAS or Pre-signal operation, not both. For this
reason, if the PAS Delay timer is set with a value greater than 000 and then the Pre-Signal Delay
timer is set with a value greater than 000, the PAS Delay timer will be automatically reset to 000.
Only one of the two timers can have a delay time set for it.
A delay can be added prior to declaring a waterflow type of alarm. Be careful to include any built-
TIMER
in delays of the waterflow device. The factory default setting for Waterflow delay is 000 for no
1=PAS DELAY
000
delay. To select a Waterflow delay of 01 to 90 seconds for all devices programmed for Waterflow
2=PRE SIGNAL
000
delay, press 3 while viewing Timer Screen #1. The following screen will be displayed:
3=WATERFLOW
000
Timer Screen #1
A flashing cursor is positioned in the lower left corner of the display. Enter a delay time consisting
of two digits, such as 25 for twenty-five seconds. Upon entering the second digit, the time delay
will be stored in the control panel memory and the display will return to the Delay Screen which
will indicate the new delay time.
82
Pre-signal Delay
RANGE 0-180 SECONDS
Waterflow Delay
RANGE 0-90 SECONDS
PRESIGNAL DELAY
Pre-signal Delay Screen
WATERFLOW DELAY
Waterflow Delay Screen
FireWarden 100-2/E — P/N 52778:A 11/04/2005
Master Programming Level