Honeywell NOTIFIER FireWarden-100-2 Instruction Manual page 49

Fire alarm control panel
Table of Contents

Advertisement

Master Programming Level
Type
To select the type of detector being programmed, press the 2 key while viewing the Edit Detector
EDIT DETECTOR
Screen #2. This will cause the control panel to display the following Detector Type Screens:
1=ENABLED
2=TYPE
3=VERIFICATION
Edit Detector Screen #2
Pressing the down arrow key will display additional detector types as indicated in the following
table.
While viewing either Detector Type screen, select the type of detector being programmed by
pressing the corresponding keyboard number key. The display will return to Edit Detector Screen
#2 and indicate the selection next to the Type option.
NOTE: If a detector is selected to be a SUPERV DUCTP type, it will function like a supervisory
point not a fire alarm point. The supervisory LED and supervisory relay will activate, not the fire
alarm LED or alarm relay, if the detector senses smoke.
Verification
Alarm verification is used to confirm that a smoke detector activation is a true alarm condition and
not a false alarm. This feature is selected by pressing 3 while viewing the Edit Detector Screen #2
so that the display reads Verification On. Each time the 3 key is pressed, the display will toggle
between Verification On and Verification Off. For a detailed description, refer to "Alarm
Verification (None or One Minute)" on page 134.
Walktest
The Walktest feature allows one person to test the system devices without the necessity of manually
EDIT DETECTOR
1=WALKTEST
resetting the control panel after each device activation. To enable a device for the Walktest feature,
2=PAS
press 1 while viewing the Edit Detector Screen #3 until the display reads Walktest Yes. Each press
3=PRE-SIGNAL
of the 1 key will cause the display to toggle between Walktest Yes and Walktest No. Refer to
Edit Detector Screen #3
"Walktest" on page 134.
PAS
The PAS (Positive Alarm Sequence) option will program the detector to delay panel activation
(including alarm relay and communicator) for a period of 15 seconds plus a programmable time of
up to 3 minutes. Zone 97, however, will activate immediately and may be used to connect a
FireWarden 100-2/E — P/N 52778:A 11/04/2005
1=SMOKE(PHOTO)
2=USER-DEFINED-1
3=SMOKE (ION)
Detector Type
Smoke Photo
User-Defined-1
Smoke Ion
User-Defined-2
Heat Detect
User-Defined-3
Smoke DuctP
User-Defined-4
Superv-DuctP
User-Defined-5
Future
Future
DETECTOR TYPE
Detector Type Screen #1
Action When Activated
Fire Alarm
same as previous (Smoke Photo)
Fire Alarm
same as previous (Smoke Ion)
Fire Alarm
same as previous (Heat Detect)
Fire Alarm
same as previous (Smoke DuctP)
Supervisory, latching
same as previous (Superv DuctP)
not used
not used
Programming
49