Ul Power-Limited Wiring Requirements - Honeywell NOTIFIER FireWarden-100-2 Instruction Manual

Fire alarm control panel
Table of Contents

Advertisement

Installation

2.7 UL Power-limited Wiring Requirements

Power-limited and nonpower-limited circuit wiring must remain separated in the cabinet. All
power-limited circuit wiring must remain at least 0.25" (6.35 mm) away from any nonpower-
limited circuit wiring and nonpower-limited circuit wiring must enter and exit the cabinet through
different knockouts and/or conduits. A typical wiring diagram for the NFW2-100 is shown below.
*Ferrite Beads
AC Power
Grounding Stud
*Ferrite Bead Installation
Per FCC requirements, ferrite beads are required for the DC Power Outputs, Remote Power Supply Sync, ACS Output and SLC
Circuit.
Wrap wire around ferrite bead as shown.
Figure 2.11 Typical UL Power-limited Wiring Requirements
32
Power-limited Circuits
Nonpower-limited Circuits
Ground Strap
To Batteries
UL Power-limited Wiring Requirements
Power-limited Circuits
Nonpower-limited Circuits
*Ferrite Beads
Close ferrite bead.
FireWarden 100-2/E — P/N 52778:A 11/04/2005
Power-limited Circuits
maintain minimum
0.25" between power-
limited and nonpower-
limited circuits wiring
Nonpower-limited
Circuits