2: How To Use Table 7.3 On Page 160 To Calculate System Current Draw - Honeywell NOTIFIER FireWarden-100-2 Instruction Manual

Fire alarm control panel
Table of Contents

Advertisement

Calculating the System Current Draw
When calculating current draw and the battery size, note the following:
• 'Primary' refers to the main power source for the control panel
• 'Secondary' refers to the control panel's backup batteries
• All currents are given in amperes (A). Table 7.2 shows how to convert milliamperes and
microamperes to full amperes.
To convert...
Milliamperes (mA) to
amperes (A)
Microamperes (
amperes (A)
7.3.2 How to Use Table 7.3 on page 160 to Calculate System
Current Draw
Use Table 7.3 on page 160 to calculate current draws as follows:
1.
2.
3.
4.
5.
Following are the types of current that can be entered into Table 7.3 on page 160:
• Calculation Column 1 - The primary supply current load that the control panel must
support during a non-fire alarm condition, with AC power applied.
• Calculation Column 2 - The primary supply current load that the control panel must
support during a fire alarm condition, with AC power applied.
• Calculation Column 3 - The standby current drawn from the batteries in a non-fire alarm
condition during a loss of AC power.
FireWarden 100-2/E — P/N 52778:A 11/04/2005
Table 7.2 Converting to Full Amperes
µ
A) to
Enter the quantity of devices in all three columns
Enter the current draw where required. Refer to the Device Compatibility Document for
compatible devices and their current draw
Calculate the current draws for each in all columns
Sum the total current for each column
Copy the totals from Column 2 and Column 3 to Table 7.4 on page 161
Multiply
mA x 0.001
3 mA x 0.001 = 0.003A
µ
A x 0.000001
300
Power Supply Calculations
Example
µ
A x 0.000001 = 0.0003 A
159

Advertisement

Table of Contents
loading

This manual is also suitable for:

Notifier firewarden-100-2e

Table of Contents