Important: When a Notification Appliance Circuit with a mix of audible and visual devices is
programmed for silenceable and the synchronization feature is selected, only the audible devices
will be turned off if the Silence key is pressed. The visual devices (strobes, etc.) will continue to
operate.

4.17 Coded Operation

The NAC circuits resident on the control panel main circuit board can be programmed for coded
operation. The available pulse rates which can be programmed for coded operation are as follows:
• Continuous:
• March Time:
• Temporal Code: Pulses at ½ second On, ½ second Off, ½ second On, ½
• California Code: 10 seconds On, 5 seconds Off
• Two-Stage

4.18 Presignal

Presignal option programs an initiating device to delay the activation of NACs and/or control
modules while allowing visual verification by a person. Once a detector or monitor module
triggers an alarm, the onboard piezo sounds immediately, but the NACs are not activated for a user
programmed time duration of up to three minutes. Note that the alarm relay and communicator will
respond to the initial alarm immediately. In addition, Zone 98 will activate. This zone can be
programmed to a control module which may be used to activate a sounder or indicator which the
installer designates as a Presignal indication. Do not assign Zone 98 to a Notification Appliance
Circuit when using this zone to indicate a Pre-signal condition.
After the programmed delay, the NACs will activate if the source of the alarm is not cleared. Note
that if a second alarm occurs during the programmed time delay, the alarm will be processed
immediately, causing activation of the appropriate output zones. The events which occur upon
Presignal activation are as follows:
• onboard piezo sounds immediately
• control panel LCD display will indicate a presignal event and the active point
• control points programmed to Zone 98 will activate
• annunciators (if enabled) will sound the local piezo, and pulse the alarm LED and zone LED
• outputs (NACs and control modules) of associated zones will be inhibited from activating
for a user programmed time delay of up to three minutes
• second alarm occurring anytime during the time delay will cause immediate activation of all
associated outputs
Presignal does not affect monitor modules programmed as waterflow, supervisory, process
monitoring or remote switches. Presignal operation requires the approval of the local Authority
Having Jurisdiction.

4.19 Positive Alarm Sequence

PAS (Positive Alarm Sequence) option will program a smoke detector to delay panel activation
(including alarm relay and communicator) for a period of 15 seconds. Zone 97, however, will
activate immediately and may be used to connect a signaling device to indicate PAS activation. Do
not assign Zone 97 to a Notification Appliance Circuit when using this zone to indicate a PAS
condition.
132
Steady output with no pulsing
Pulses at 120 ppm (pulses per minute)
second Off, ½ second On, 1½ second Off
Pulses at 20 ppm (pulses per minute) for 3 or 5 minutes depending on
programming and then changes to on steady (Refer to Two-Stage, p. 87)
FireWarden 100-2/E — P/N 52778:A 11/04/2005