Master Programming Level
MODULES
1=ADD
2=DELETE
3=EDIT
Modules Screen
FireWarden 100-2/E — P/N 52778:A 11/04/2005
Edit Module Screen for Control Modules
The programmer can change a module's existing or factory default programming by pressing 3 in
the Modules Screen. The following screen will be displayed:
ENTER MODULE ADDRESS
***
A flashing cursor will appear in the position of the first asterisk to the left.
The programmer keys in the three digit module address, such as 002. When the last digit is keyed-
in, if the selected address corresponds to a control module, a screen displaying information about
the control module with the selected address will be displayed as illustrated in the following:
NORMAL
In the preceding example:
• Normal - indicates that the module with the selected address is physically installed on the
SLC and communicating with the control panel (enabled)
• <ADJ><NOUN> - represents the adjective and noun, which have been programmed,
describing the location of the displayed device
• Control - indicates that the selected module is a control module
• S or * - represents Silenceable (S) or Nonsilenceable (*)
• W or * - represents Waterflow Timer Delay (W = Waterflow Timer Delay enabled, * =
Waterflow Timer Delay disabled)
• ZNNN - represents the first of five possible software zones that the module is assigned to
(NNN = the three digit zone number from 000 - 099)
• 1M002 - represents the Loop, Device type and Device address (1 = SLC Loop, M=Module
and 002 = Module Address 02)
EDIT MODULE
Edit Module Screen
CONTROL
<ADJ><NOUN>
ZNNN
SW
1M002
Edit Control Screen #1
Programming
65